When the automatic speed is selected, and there is an air quality probe, the control board adjusts the fan speed
according to the deviation from the desired air quality (the greater the deviation from the minimum air quality set,
the greater the speed).
The minimum and maximum air quality set points can be modified through the parameters P123 and P124 (by
default 30 and 70%); they express a percentage corresponding to the 0-10V input signal with respect to 10V:
check the output curve of the probe to obtain the correspondence; for example, for a CO2 probe with 0-10V output
and measurement range 0-2000 ppm, 30% corresponds to a signal of 3V and therefore to 600 ppm, while 70%
corresponds to a signal of 7V and therefore to 1400 ppm.
The automatic speed control as a function of air quality is not available when the unit is equipped with constant flow
or pressure control.
VELOCITÀ AUTOMATICA CON TEMPERATURA
/ AUTOMATIC SPEED WITH TEMPERATURE
Quando è selezionata la velocità automatica, la scheda di controllo provvede a regolare la velocità dei ventilatori in
funzione dello scostamento della temperatura ambiente dal set point Estate/Inverno (maggiore è lo scostamento,
maggiore è la velocità).
Il controllo della velocità in riscaldamento (inverno) è attivo soltanto se è presente un elemento riscaldante
(resistenza o batteria ad acqua calda) nella sezione di post-trattamento; il controllo della velocità in raffreddamento
(estate) è attivo soltanto se è presente un elemento refrigerante (batteria ad acqua fredda) nella sezione di post-
trattamento. Il controllo automatico della velocità in funzione della temperatura non è disponibile nel caso in cui
l’unità è dotata di controllo a portata o pressione costante.
When the automatic speed is selected, the control board adjusts the fan speed according to the ambient temperature
deviation from the Summer/Winter set point (the greater the deviation, the greater the speed).
The speed control in heating (winter) is only active if there is a heating element (heating element or hot water coil)
in the post-treatment section; the speed control in cooling (summer) is only active if there is a cooling element (cold
water coil) in the post-treatment section. The automatic temperature speed control is not available if the unit is
equipped with constant flow or pressure control.
SELEZIONE MODALITÀ ESTATE / INVERNO E IMPOSTAZIONE DEI RELATIVI SET POINT
/ SELECTING SUMMER / WINTER MODE AND SETTING THE RELATIVE SET POINTS
Tutte le regolazioni termiche effettuate dalla scheda di controllo dipendono da quale modalità è attiva:
•
in modalità invernale sono attive tutte le funzioni di riscaldamento, ovvero:
- azionamento dell’eventuale resistenza di post-riscaldo o batteria ad acqua calda, con relativa
regolazione della velocità automatica in funzione della temperatura
- free-heating
- protezione antigelo
•
in
modalità estiva
sono attive tutte le funzioni di raffreddamento, ovvero:
- azionamento dell’eventuale batteria ad acqua fredda, con relativa regolazione della velocità
automatica in funzione della temperatura
- free-cooling
Ovviamente le funzioni di riscaldamento sono disattivate in modalità estiva e le funzioni di raffreddamento sono
disattivate in modalità invernale.
La modalità in cui si trova l’unità è segnalata continuamente dal controllo remoto attraverso i simboli Sole (estate)
e Fiocco di neve (inverno)
Il passaggio tra la modalità estiva e quella invernale può avvenire nei seguenti modi: