Menu Outputs
25
Particularities of output 14
Output 14 basically serves as a data link (DL-Bus9 but can also be used as a switch output for switch-
ing an external relay and can be configured accordingly (
unused / SWITCH.OUTP / DATA LINK
).
Output 14 as data link:
Output 14 serves as a data link (DL bus) for the recording of measured values ("data logging") via
C.M.I. or D-LOGG and/or as a bus line for various sensors.
If the control receives data via the network, it is possible to send a second data record with the net-
work input data via DL. In this case the data logger recognises the second data record as a virtual
second UVR1611 controller. However this option can only be used if the data logger's second DL
input is unused.
OUTPUT STATUS:
TYPE: DATA LINK
DESIGNATOR
GROUP: General
DES: Data link
NETW.INP.=>DL.: no
Output 14 as data line / DL-bus
For a “yes” input: Network inputs are output to the DL bus as a
second data record
Output 14 as switching output:
When required, output 14 together with an external 12 V / 20 mA relay (laid to ground) can be used as
an additional switch output. The relay must be fitted with a suitable free-wheeling diode.
Recording of the measured values with the data logger and capturing sensors via the DL bus link are
not possible in this mode.
With device type UVR1611E (special type for control cabinet fitting) output 14 is able to be used
simultaneously
as a switch output and a DL link (DL bus). That is why for this type of device in the
setting "
UVR1611E: yes
" the data link can be activated in addition to the switch output. This option
may only be activated for type UVR1611E and results in a malfunctioning of the output with other
types of devices.
OUTPUT STATUS:
TYPE: SWITCH.OUTP
DESIGNATOR
GROUP: General
DES: HC Pump
DELAY: 0 sec
RUN-ON: 0 sec
UVR1611E: no
NETW.INP.=>DL.: no
Output 14 as switch output
This option may only be activated with type UVR1611E.