Output variable
A total of 16 digital and 16 analogue network outputs can be programmed. All of the input and output
statuses, output variables for the functions, network status, sensor status, and the status of messages
can be used.
DIGITAL NETW. OUTPUT
-------------------
OUTPUT 1:
Source: HTG CIRC.1
2: Pump Status
Status: ON
Target: CAN
Example:
The digital network output 1 has been allocated the
status of heating circuit pump 1, the current pump status is "ON"
With input Target "DL" it is possible, to switch specific sensors on
or off via the DL bus. More precise instructions are contained in
the data sheets for these sensors.
Parameterizing of the analogue output variables takes place in the same way.
Transmission conditions
:
This menu determines the conditions for the transmission of output variables.
DIGITAL OUTP.: 1..16
with change yes
Block. time: 10 Sec
Interv tm mtr: 5 Min
ANALG. OUTP.: 1..4
with change > 30
Block. time: 10 Sec
Interv tm mtr: 5 Min
…
…
The transmission conditions are divided into five groups:
digital network outputs 1-16
analogue network outputs 1-4, 5-8, 9-12, and 13-16
with change yes/no:
Transmission of a digital message if status is changed.
with change > 30:
If the last analogue value transmitted has been changed by more than
3.0 K, the data are transmitted again (= 30 because numbers are trans-
mitted without a comma).
Block. time 10 sec:
If the value is changed within 10 seconds of the last transmission by more
than 30 (3,0K), the value is not transmitted anew for another 10 seconds.
Interv tm mtr 5 min.:
The value is transmitted every five minutes even if it has not changed by
more than 30 (3.0K) since the last transmission.