Menu Outputs
23
MENU Outputs
The menu
"Outputs“
primarily serves for the switching between the automatic and manual mode of
the outputs. As in the status line of the outputs (top symbol line on the display) it is not possible to
share information concerning the speed stages (if active), this indication was put down in the output
menu. The parameterizing of all used outputs is effected by employing the following procedure:
The line “
Outputs
” has already been selected and then pressed the scroll-wheel. Hereby the indica-
tion example is as follows:
1: Solar pump1
MAN./ON PAR?
Pump solar 1 is switched on in
manual mode.
2: HC pump1
AUTO/OFF PAR?
Speed stage: 0
Heating circuit pump 1 is switched off in
automatic mode.
3: HC mixer1
AUTO PAR?
open: OFF
4: clse: OFF
Output A4 together with A3 is configured as a mixer output.
5: -----
-----
PAR?
Input 5 has to be set before.
and so on
Hence, the output 1 as solar pump, the output 2 as heating circuit pump and the outputs 3 and 4 as
mixer (open/closed) were already determined.
According to the example the outputs 1 and 4 are set to the automatic mode and indicate the current
operating state (OFF). If the pointer is placed behind that position, the switching to manual mode
on/off is possible (pressing the wheel / selecting the state / pressing the wheel). The current status of
the output is immediately shown up in the status line of the outputs. As the speed control function at
output 1 is active, the current speed stage is also faded in. This only can be changed in manual mode
for experimental purposes.
As seen at the output 5, neither the “Designator” nor the status of the output appears before the pa-
rameterizing (similar to the parameterizing of the inputs). Thus, the corresponding symbol would also
be missing in the top display line of the output status.
If e.g. the solar pump is to be assigned to the (not yet determined) output 1, the arrow must be in-
duced to the corresponding entrance of the parameterizing level
PAR?
by means of the scroll-wheel.
Pressing the wheel causes the entering and the following indication appears:
TYPE: unused
First, it has to be determined which basic characteristic (TYPE) the output should own. Possible
selections:
SWITCH.OUTP
= Output only can effect switches (no speed control)
SPEED CTRL
= Output is prepared for the speed control
At the outputs 3, 8, 10 and 12 the suggestion MIXER appears instead of the type
SPEED CTRL
, while
each first output means “Mixer open” and the next-following (4, 9, 11 and 13) “Mixer closed”. In other
words, if output 4 is defined as switching output and if output 3 is parameterized afterwards as mixer,
output 4 automatically becomes the second mixer output!