Function control
98
Entire menu view:
(No
error)
(With
error)
DES: FUNC CTRL
INPUT VARIABLE:
OUTPUT VARIABLE:
PARAMETER:
T.collector OK
57.4 °C
T.DHW1
OK
48.9 °C
DIFFEREN.
OK
8.5 K
Save error: yes
Delete error disp.?
BEZ.:
KONTR.SOL1
INPUT VARIABLE:
OUTPUT VARIABLE:
PARAMETER:
T.Collector
ERROR
9999 °C lead brk
T.DHW1
OK
48.9 °C
DIFFEREN.
ERROR
9999 K too high
Save error: yes
Delete error disp.?
The parameter menu contains the following if monitoring a difference:
Error if over
at least 30 min
Error minimum time setting
CVa – CVb > 50 K
Difference threshold setting
Or if value a is being monitored, for example:
Error if over
at least 30 Min
Error minimum time setting
CVa
> 30°C
Error threshold setting
Troubleshooting
:
"Save error: yes"
ERROR
remains displayed even after the remedy has been provided until the user
presses the scroll wheel to confirm "Delete error display?" If the error continues after deletion, the
message will be reissued after a certain delay.
"Save error: no"
ERROR
is automatically deleted once the error has disappeared.
If an output has been assigned in the output variables, it responds the same as the display.
The status lines of the function control should also be entered in the function overview using the user
interface editor. In this way, users will always have the information they need in their menu.