Radiation sensor
GBS 01
- non-standard accessory: Indicates a sensor input if
a radiation sensor is used.
If the radiation sensor exceeds the radiation
threshold (RTH), the priority timer is launched.
Without the radiation sensor, the launch is based on the collector temperature.
(ex works = --)
Setting range:
S1 to S6
Input of radiation sensor
E1 to E9
Value of the external sensor
GBS
--
no
radiation
sensor
RTH
Radiation
value
(
r
adiation
th
reshold) in W/m
2
above which rinsing is allowed.
Without a radiation sensor, the computer calculates the necessary temperature
increase for the long-term mean that launches rinsing from this value.
(ex works
= 150W/m
2
)
Setting range:
0 to 990W/m
2
in increments of 10W/m
2
OPS
O
ut
p
uts used for
r
insing. If a control output is allocated to the output, then the
analog stage 100 is additionally output at this control output.
(ex works = OPS1)
Setting range: combination of all outputs (such as OPS1, OPS23, OPS13…)
WTL
W
aiting
t
ime of
l
ow priority. This is the time in which the collector should reach
the temperature necessary for priority operation. If the waiting time is set to 0
the solar priority timer is deactivated. (ex works = 5 min)
Setting range:
0 to 99 minutes in increments of 1 min
PRT
P
ump
r
un-
t
ime of low-priority. If the solar radiation to switch to priority is not
sufficient, the low priority is allowed again for this time.
If the pump run-time PRT is set to 0, the low priority is only allowed when
the maximum threshold for priority is reached (= absolute priority).
(ex works = 20 min)
Setting range:
0 to 99 minutes in increments of 1 min