Program 608 - 2 generators on 2 con burner requirement
No
diagram
available!
Program 608:
Pump
A1
runs when:
S1
is greater than the threshold
min1
and
S1
is greater than
S3
by the difference
diff1
and
S3
has not exceeded the threshold
max1
.
or
S2
is greater than the threshold
min2
and
S2
is greater than
S3
by the difference
diff1
and
S3
has not exceeded the threshold
max1
.
Pump
A2
runs when:
S1
is greater than the threshold
min1
and
S1
is greater than
S4
by the difference
diff2
and
S4
has not exceeded the threshold
max2
.
or
S2
is greater than the threshold
min2
and
S2
is greater than
S4
by the difference
diff2
and
S4
has not exceeded the threshold
max2
.
Output
A3
switches on when
S6
falls below threshold
min3
.
Output
A3
switches off (dominant) when
S5
exceeds
max3
.
A1 = S1 > (S3 + diff1) & S1 > min1 & S3 < max1
or
S2 > (S3 + diff1) & S2 > min2 & S3 < max1
A2 = S1 > (S4 + diff2) & S1 > min1 & S4 < max2
or
S2 > (S4 + diff2) & S2 > min2 & S4 < max2
A3
(on)
=
S6
<
min3
A3 (off) = S5 > max3
Program 609: The burner requirement (
A3
) only occurs via sensor
S6
.
A3 (on) = S6 < min3
A3 (off) = S6 > max3
(dominant)
Program 610: As with program 608, but the burner requirement (
A3
) comes from
S2
and
S5
A3 (on) = S2 < min3
A3 (off) = S5 > max3
(dominant)
S1
S2
min1
min2
S3
S4
max1
max2
Burner
A3
S6 min3
S5 max3
Required settings:
max1
… limit TK1
S3
A1
max2
… limit TK2
S4
A2
max3
… burner req. off
S5
A3
min1
… switch-on t. boiler1
S1
A1
min2
… switch-on t. boiler2
S2
A2
min3
… burner req. on
S6
A3
diff1
… boiler1
S1
– TK1
S3
A1
… boiler2
S2
– TK1
S3
A1
diff2
… boiler1
S1
– TK2
S4
A2
… boiler2
S2
– TK2
S4
A2
diff1
A1
diff1
A1
diff2
A2
diff2
A2