Program 593:
Program 593:
Pump
A1
runs if:
S1
is greater than threshold
min1
and
S1
is higher than
S3
by the difference
diff1
and
S3
has not exceeded threshold
max1.
or
S1
is greater than threshold
min1
and
S1
is higher than
S4
by the difference
diff1
and
S4
has not exceeded threshold
max2.
The pump
A2
runs if:
S2
is greater than threshold
min2
and
S2
is higher than
S3
by the difference
diff2
and
S3
has not exceeded threshold
max1.
or
S2
is greater than threshold
min2
and
S2
is higher than
S4
by the difference
diff2
and
S4
has not exceeded threshold
max2.
Load pump
A3
runs if:
S5
is greater than threshold
min3
and
S5
is higher than
S6
by the difference
diff3
and
S6
has not exceeded threshold
max3.
A1 = S1 > (S3 + diff1) & S1 > min1 & S3 < max1
or
S1 > (S4 + diff1) & S1 > min1 & S4 < max2
A2 = S2 > (S3 + diff2) & S2 > min2 & S3 < max1
or
S2 > (S4 + diff2) & S2 > min2 & S4 < max2
A3 = S5 > (S6 + diff3) & S5 > min3 & S6 < max3
Required settings:
max1
… limit TK1
S3
A1,
A2
max2
… limit TK2
S4
A1,
A2
max3
… limit TK3
S6
A3
min1
… switch-on t. boiler1
S1
A1
min2
… switch-on t. boiler2
S2
A2
min3
… switch-on temp. coll.
S5
A3
diff1
… boiler 1
S1
– TK1
S3
A1
… boiler 1
S1
– TK2
S4
A1
diff2
… boiler 2
S2
– TK1
S3
A2
… boiler 2
S2
– TK2
S4
A2
diff3
… coll.
S5
– TK3
S6
A3
S1
S2
min1
min2
S3
S5
S4
max1
min3
max2
S6
max3
diff2
A2
diff1
A1
diff1
A1
diff2
A2
diff3
A3