The feed pump
A2
runs when:
S3
is greater than the threshold
min2
and
S3
is greater than
S2
by the difference
diff2
and
S2
has not exceeded the threshold
max2
.
A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1
A2 = S3 > (S2 + diff2) & S3 > min2 & S2 < max2
All pr2:
If sensor
S2
has reached
max1
(or if
S4
has reached threshold
max3
along with all programs
+4), pump
A2
is switched on, and pump
A1
keeps running. This provides a cooling function
for the boiler / heater without causing standstill temperatures in the collector.
All pr4:
In addition, if
S4
exceeds the threshold
max3,
pump
A1
is switched off.
All pr8:
With re-cooling activated (all pr2)
A3
runs concurrently.
Program 96 - Buffer and hot water tank load via boiler fired with solid fuel
Program 96:
Pump
A1
runs when:
S1
is greater than the threshold
min1
and
S1
is greater than
S2
by the difference
diff1
and
S2
has not exceeded the threshold
max1
.
Feed pump
A2
runs when:
S3
is greater than the threshold
min2
and
S3
is greater than
S4
by the difference
diff2
and
S4
has not exceeded the threshold
max2
.
A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1
A2 = S3 > (S4 + diff2) & S3 > min2 & S4 < max2
S1
S3
min1
min2
S2
S4
max1
max2
diff2
A2
diff1
A1
Required settings:
max1
… limit TK1
S2
A1
max2
… limit TK2
S4
A2
max3
… see all pr2
min1
… switch-on temp. boiler
S1
A1
min2
… switch-on temp TK1.
S3
A2
min3
… see all pr2
diff1
… boiler
S1
– TK1
S2
A1
diff2
… TK1
S3
– TK2
S4
A2
diff3
… see all pr1, +2