54
Program 611:
As with program 608, but the burner requirement (
A3
) comes from sensor
S2
.
A3 (on) = S2 < min3
A3 (off) = S2 > max3
(dominant)
Program 612:
As with program 608, but the burner requirement (
A3
) comes from
S4
and
S5
.
A3 (on) = S4 < min3
A3 (off) = S5 > max3
(dominant)
Program 613:
As with program 608, but the burner requirement (
A3
) comes from sensor
S4
.
A3 (on) = S4 < min3
A3 (off) = S4 > max3
(dominant)
All pr8:
The pump
A1
runs if:
S1
is greater than threshold
min1
and
S1
is higher than
S3
by the difference
diff1
and S3 has not exceeded threshold
max1
.
or
S1
is greater than threshold
min1
and
S1
is higher than
S4
by the difference
diff1
and
S4
has not exceeded threshold
max2.
The pump
A2
runs if:
S2
is greater than threshold
min2
and
S2
is higher than
S3
by the difference
diff2
and
S3
has not exceeded threshold
max1.
or
S2
is greater than threshold
min2
and
S2
is higher than
S4
by the difference
diff2
and
S4
has not exceeded threshold
max2.
A1 = S1 > (S3 + diff1) & S1 > min1 & S3 < max1
or
S1 > (S4 + diff1) & S1 > min1 & S4 < max2
A2 = S2 > (S3 + diff2) & S2 > min2 & S3 < max1
or
S2 > (S4 + diff2) & S2 > min2 & S4 < max2
S1
S2
min1
min2
S3
S4
max1
max2
Burner
A3
S6 min3
S5 max3
Required settings:
max1
… limit TK1
S3
A1,
A2
max2
… limit TK2
S4
A1,
A2
max3
… burner req. off
S5
A3
min1
… switch-on t. boiler1
S1
A1
min2
… switch-on t. boiler2
S2
A2
min3
… burner req. on
S6
A3
diff1
… boiler1
S1
– TK1
S3
A1
… boiler1
S1
– TK2
S4
A1
diff2
… boiler2
S2
– TK1
S3
A2
… boiler2
S2
– TK2
S4
A2
diff2
A2
diff1
A1
diff2
A2
diff1
A1
Содержание UVR 63
Страница 1: ...UVR63 Version 2 2 EN Triple loop universal controller Operation Installation instructions en ...
Страница 2: ......
Страница 72: ...72 Schematic representation of setting values ...
Страница 123: ......