45
Program 496 - 1 consumer and 3 feed pump functions
Program 496:
Solar pump
A1
runs when:
S1
is greater than the threshold
min1
and
S1
is greater than
S2
by the difference
diff1
and
S2
has not exceeded the threshold
max1
.
The feed pump
A2
runs when:
S3
is greater than the threshold
min2
and
S3
is greater than
S2
by the difference
diff2
and
S2
has not exceeded the threshold
max2
.
The feed pump
A3
runs when:
S4
is greater than the threshold
min3
and
S4
is greater than
S2
by the difference
diff3
and
S2
has not exceeded the threshold
max3
.
A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1
A2 = S3 > (S2 + diff2) & S3 > min2 & S2 < max2
A3 = S4 > (S2 + diff3) & S4 > min3 & S2 < max3
Required settings:
max1
… limit TK
S2
A1
max2
… limit TK
S2
A2
max3
… limit TK
S2
A3
min1
… switch-on temp. coll.
S1
A1
min2
… switch-on t. heat source
S3
A2
min3
… switch-on temp. boiler
S4
A3
diff1
… coll.
S1
– TK
S2
A1
diff2
… heat source
S3
– TK
S2
A2
diff3
… boiler
S4
– TK
S2
A3
S1
S3
S4
min1
min2
min3
S2
max1
max2
max3
diff2
A2
diff1
A1
diff3
A3
S3
A2
A3
S1
A1
S2
S4