Program 592 - 2 generators on 2 con independent differential loop
No diagram available!
Program 592:
Pump
A1
runs when:
S1
is greater than the threshold
min1
and
S1
is greater than
S3
by the difference
diff1
and
S3
has not exceeded the threshold
max1
.
or
S2
is greater than the threshold
min2
and
S2
is greater than
S3
by the difference
diff1
and
S3
has not exceeded the threshold
max1
.
Feed pump
A2
runs when:
S1
is greater than the threshold
min1
and
S1
is greater than
S4
by the difference
diff2
and
S4
has not exceeded the threshold
max2
.
or
S2
is greater than the threshold
min2
and
S2
is greater than
S4
by the difference
diff2
and
S4
has not exceeded the threshold
max2
.
The feed pump
A3
runs when:
S5
is greater than the threshold
min3
and
S5
is greater than
S6
by the difference
diff3
and
S6
has not exceeded the threshold
max3
A1 = S1 > (S3 + diff1) & S1 > min1 & S3 < max1
or
S2 > (S3 + diff1) & S2 > min2 & S3 < max1
A2 = S1 > (S4 + diff2) & S1 > min1 & S4 < max2
or
S2 > (S4 + diff2) & S2 > min2 & S4 < max2
A3 = S5 > (S6 + diff3) & S5 > min3 & S6 < max3
Required settings:
max1
… limit TK1
S3
A1
max2
… limit TK2
S4
A2
max3
… limit TK3
S6
A3
min1
… switch-on t. boiler1
S1
A1
min2
… switch-on t. boiler2
S2
A2
min3
… switch-on temp. coll.
S5
A3
diff1
… boiler 1
S1
– TK1
S3
A1
… boiler 2
S2
– TK1
S3
A1
diff2
… boiler 1
S1
– TK2
S4
A2
… boiler 2
S2
– TK2
S4
A2
diff3
… coll.
S5
– TK3
S6
A3
S1
S2
min1
min2
S3
S5
S4
max1
min3
max2
S6
max3
diff1
A1
diff1
A1
diff2
A2
diff2
A2
diff3
A3