12
ESR21, ESR31, UVR61-3, UVR63 and UVR63-H
Adjustment of the measurements takes place in the menu
EXT DL
(external sensors)
Example:
The external sensor 1 has address 1, the measured room temperature
is imported without offset values (index 2).
In the controllers ESR31, UVR61-3, UVR63 and UVR63-H (version 5.0 up to 7.1), only the measured
room temperature can be evaluated without offset values (index 2); the slider switch and the rotary
knob have no purpose for these controllers. This value can subsequently be allocated to a sensor val
-
ue (menu ENTER/Men – SENSOR).
The room humidity value is indicated in these controllers as a dimensionless value without a decimal
point (e.g. 35.5% -> Controller display: 355).
The values of indices 1 and 5 would be indicated with "999” and therefore cannot be used.
The menu option "EXT DL" is only available in the following controllers:
• UVR63-H from version 5.0
• UVR63 from version 1.0
• UVR61-3 from version 5.0
• ESR31 from version 1.0
• ESR21 from version 5.0
Entry of an offset value for sensor correction OFFSET
Offset values can be set for the measured values for temperature, room humidity and ambient air
pressure.
Entry T 0.0 = no offset value selected, therefore
no sensor correction
Factory setting: T 0.0
After a long key press "0.0" flashes
Selection of the desired offset value via a short
key press.
Confirmation of the desired value via a long key
press
Entry T +0.7 = The room temperature value dis
-
played and transmitted to the controller is in
-
creased by 0.7 K.
Adjustment range:
- 4,0K to +4,0K
Further short presses of the button will display
the offset values for room humidity and air pres
-
sure (
P
).