11
Index specification
To process sensor values on the controller, specification and selection of the sensor address (1-8)
and
the index (1-11) is necessary.
Indices can be selected for the following values:
UVR16x2, RSM610, CAN-I/O45:
The measured values are parameterised in the menu
„DL bus“.
In
TAPPS2
, a DL input is programmed with the corresponding address and index.
If the
measured variable
is set to "
Automatic
", no further settings are required here.
Index Value
1
Room temperature
with offset values
for +/- adjustment the dip switch (to evaluate „RAS“
on controllers
UVR1611
and
UVR63-H
(min. version 7.2))
2
Measured room temperature (
without offset values
of the +/- adjustment and the slider
switch (e.g. for the controller UVR61-3)
3
Relative room humidity
4
Dew point temperature
5
Fixed value 20°C
with offset values for +/- adjustment and the dip switch (used as
remote
adjuster
for controllers UVR16x2, UVR1611 and UR63-H)
6
Unused
7
Air pressure in mbar
8
Absolute humidty
9/10
Unused
11
Room temperature
with offset values
for +/- adjustment and the dip switch (for evaluating
„RAS“
in controllers
UVR16x2, RSM610, CAN-I/O45
)
12
Room temperature
without offset values
of +/- adjustment, with dip switch position (only
x2 devices)
13
Offset value of +/- adjustment, range -4 to +4 K (only x2 devices)
14
Serial number of room sensor (only x2 devices)
15
Software version of room sensor (only x2 devices)