10
Time before jumping back to the first display TIME R
Entry 0 = no jumping back to the first display
Factory setting: 0
„0“ flashes after a long key press
Selection of the desired time via a short key press. Confirma
-
tion of the desired time via a long key press.
Entry 60 = After 60 seconds without pushing of the button
jumping back from one of the additional programmed values
to the first display value (room temperature) occurs.
Adjust
-
ment range:
0-200 sec in steps of 1 second.
The jump back occurs only from the additionally programmed display values, not from the one of the
base values.
Address in the DL-bus network DL ADR
Upon request by controller
ESR31, UVR63
(min. version 1.0),
ESR21, UVR61-3
and
UVR63-H
(min.
version 5.0),
UVR1611
(min. version A3.00), plus
UVR16x2, RSM610
and
CAN-I/O45
, the sensor re
-
turns the corresponding measured value. The request consists of the address of the sensor and the
index number of a measured value.
Each device in the DL-Bus network must have its own ad
-
dress so that it can send values to a controller.
Factory setting: DL 1
„1“ flashes after a long key press
Selection of the desired address via a short key press.
Adjustment range:
DL 1 to DL 8
Confirmation of the desired address via a long key press.
Among those controllers that have no bidirectional data link (those for which the
RAS+DL
can only
be used as a
remote display,
e.g. HZR65), this menu option is still displayed but has no effect and
should therefore be ignored.
Note: Of the continuous display TIME N is activated (
≠
0), then TIME R has no effect.