The UPS is equipped with a redundant auxiliary power supply that enables the UPS to run on an automatic bypass even when a
failure occurs in the main auxiliary power supply. If a fault occurs in the UPS shutting off the main auxiliary power supply, the
load is powered by the automatic bypass. The multiprocessor board and the control panel are not powered so the LEDs and the
display are off.
P
ROGRAMMABLE
A
UXILIARY
S
OCKET
(
POWER SHARE
)
The UPS has an output socket which enables the automatic disconnection of the load in certain operating conditions. The
events that determine the automatic disconnection from the Power share socket can be selected by the user using the
UPSTools configuration software (see the sections
Configuration Software
and
UPS Configuration
).
For example, the load can be disconnected after the battery has been operating for a given time, or at the pre-alarm threshold
for end of battery charging, or when an overload occurs.
Safety notes
: when the UPS is switched on, if the output switch (SWOUT) is opened, the Power share socket will
remain connected to the mains.
If the manual bypass switch (SWMB) is inserted, the output switch (SWOUT) is opened and when the UPS is
shutdown, the socket will be disconnected.
P
OWER WALK
-
IN
The UPS has a Power Walk-in mode which can be enabled and configured using the software
UPS Tools
. When the mode is
enabled and mains power is restored after a period of battery operation, the UPS starts to draw progressively from it so as not
to stress (due to the peak) any generating set installed upstream. The transient time may be set from 1 to 30 seconds. The
default value is 10 seconds. During the transient, the necessary power is drawn in part from the batteries and in part from the
mains, maintaining sinusoidal absorption. The battery charger is turned on again once the transient has passed.
R
EDUCING THE
L
OAD
(
TO
200V
AND
208V)
If the output voltage is set to 200V and 208V (see “Configuring the UPS” paragraph), the maximum power output of the UPS is
reduced with respect to its rated value, as shown in the graph below:
PRELIMINARY
86
C
ONFIGURING THE
UPS
The table below illustrates all the possible settings at your disposal to tailor the UPS to best satisfy your needs.
CP
(Control Panel)
= Indicates that the configuration can be changed not only from the configuration software but also from
the control panel.
SW
(Software) =
Indicates that the configuration may only be changed from the configuration software.
FUNCTION
DESCRIPTION
DEFAULT
POSSIBLE SETTINGS
MOD.
Output frequency
Selects rated
output frequency
50 Hz
•
50 Hz
•
60 Hz
CP
Output voltage
Selects rated
output voltage
(Phase / Neutral)
230V
•
200V *
•
208V *
•
220V
•
230V
•
240V
•
220 ÷ 240 in steps of 1V
(via software only)
CP
Operating mode
Selects one of the
5 operating modes
ON LINE
•
ON LINE
•
ECO
•
SMART ACTIVE
•
STAND-BY OFF
•
FREQUENCY CONVERTER
(via software only)
CP
Power off due to
minimum load
Automatically powers off
UPS in battery operation,
if the load is less than 5%
Disabled
•
Enabled
•
Disabled
CP
Autonomy limitation
Sets the maximum time
of operation on battery
power
Disabled
•
Disabled (complete battery
discharge)
•
1 ÷ 65000 in steps of 1 sec.
SW
Battery low prealarm
Sets the estimated
autonomy time left for
battery low warning
3 min.
1 ÷ 255 in steps of 1 min.
SW
Battery test
Sets the time interval for
automatic battery test
40 hours
•
Disabled
•
1 ÷ 1000 in steps of 1 hour
SW
Maximum load alarm
threshold
Selects the user
overload limit
Disabled
•
Disabled
•
0 ÷ 103 in steps of 1%
SW
Sound alarm
Selects the operating
mode of the sound alarm
Reduced
•
Normal
•
Reduced:
does not sound when
bypass is activated
momentarily
CP
Auxiliary socket
(power share)
Selects the operating
mode of the auxiliary
socket
Always
connected
•
Always connected
•
Disconnected after
n
seconds of
battery operation
•
Disconnected
n
seconds after the
end of discharge alarm signal
•
... (see manual of UPSTools)
SW
Battery expansion
Sets the Ah installed
(external battery
extension)
0 Ah
Min.: 0 - Max.: 999
(in steps of 1 unit)
CP
Language
Selects the display
language
English
•
English
•
Italian
•
German
•
French
•
Spanish
CP