Bonus Plus Instructions Tarm Biomass 1-800-782-9927 Version 11/14 Page 20
3.3.2 Temporary Storage
If the boiler installation is going to take place at a later date the boiler and components need to be
stored in a safe, dust-free, dry location. Moisture can damage the insulation, electrical components,
and ceramics. If boiler is subjected to this kind of environment, it could void the warranty.
3.3.3 Moving the Boiler
See
Section 6.3
Specification Data for weights and measurements of the Bonus Plus boiler.
The
boiler is heavy and large!
Moving the boiler into place requires planning and resources. The boiler
may be unloaded using a pallet jack or forklift. Alternately, it can be lifted from above by utilizing the
lifting rings welded to the top of the boiler.
3.3.4 Boiler Set-up
After the packaging is removed and the boiler is set into place, it should be checked to assure that it is
level and securely placed. Loose parts and accessories shipped with the boiler should be removed and
stored in a safe place. A copy of this manual is shipped with the boiler for reference during installa-
tion. The boiler can be set using leveling bolts located on each corner.
It is not necessary to remove the wooden shipping braces and wedges located within the boiler. They
will burn away within a few hours of initial firing.
3.4 Connections to the Boiler
The following connections must be made to the boiler, in order for it to function:
The boiler flue gas exhaust collar must be connected to the chimney system.
The heating system piping must be connected to the boiler supply and return connections.
Electrical power must be provided at the boiler electrical terminal box.
3.4.1 Chimney Connection
The connection between the boiler and the chimney system should be single wall 24 gauge (minimum)
stainless or black pipe, unless prohibited by the local code authority.
The single wall chimney connector must not pass through an attic, roof space, closet or similar
concealed space, or a floor, or ceiling.
Where passage through a wall or partition of combustible construction is desired, the installa-
tion must conform to NFPA 211.
The chimney connection pipe must be placed over the outside of the boiler’s flue gas exhaust
pipe.
A flue collar adaptor is available from Tarm Biomass.
Boiler Installation & Start-up > Setting the Boiler
CAUTION
CAUTION
☼
☼
☼
☼
Do not install a flue damper in the exhaust venting system of this unit.
Do not connect this unit to a chimney flue serving another heating appliance, unless approved by
the local code authority.
Do not connect the boiler to any air distribution duct or system.
Install vent at clearances specified by the vent manufacturer.