FY operation manual 64
13.3 Program Initial Setting
Program time format
Program execute start
address
Program execute with
repeat function ?
Program execute with
power fail function ?
Program
Initial Setting
Program execute with
wait function ?
1.
Setting program time format
Parameter
LED display
Description
Default
Level
SET9.2
Program time format
0 : hour.minute
1 : minute.second
0
Level 4
This parameter determines the time format of timer during program execution
When SET9.2 =0 , TM_n=33.23, it indicates that the execution time of this segment is 33 hours and 23 minutes
When SET9.2 =1 , TM_n=33.23, it indicates that the execution time of this segment is 33 minutes and 23 seconds
2.
Setting program execute start address
Parameter
LED display
Description
Default
Level
SET8.3
Program execute start address
0 : execute from zero
1 : execute from current PV
1
Level 4
When program starts, SV initial value will execute according to SET8.3 set value
(1) SET8.3 =0, PTN=1 PV=50.0 SV_1=100.0 TM_1=1.00(1 hour)
When program starts, SV will start to execute from 0.0, and SV shall reach SV_1 in one hour
(2) SET8.3 =1, PTN=1 PV=50.0 SV_1=100.0 TM_1=1.00(1 hour)
When program starts, SV will start to execute from PV temperature of 50.0, and SV shall reach SV_1 in one hour
3.
Setting program execute with repeat function
Parameter
LED display
Description
Default
Level
SET8.1
Program execute repeat
0 : disable repeat function
1 : Program execute repeat
0
Level 4
When program completes the execution of the final segment, and
“END” message is not shown, the program will be executed
again.
4.
Setting program execute with power failure protection function
Parameter
LED display
Description
Default
Level
SET8.2
Program execute power fail protection
0 : disable power fail protection
1 : enable power fail protection
0
Level 4
power failure during program execution, if there is power failure protection function set, controller
will execute current segment program after booting finish
Assume power failure occurring in the segment_4, ramp temperature from 100°C to 200°C, and power failure occurring
at SV=125, the program will execute from 100°C (segment_4), after controller booting finish
5.
Setting program execute with wait function
Parameter
LED display
Description
Default
Level
WAIT
Program execution standby temperature
0 : when program execute do not wait for PV
temperature
Other values : when PV=(target SV-WAIT),
program entering next segment
0.0
Level 3
When program executes, if WAIT=0.0, and SV reaches set temperature, whether PV reaches target temperature
or not, the controller will enter the next segment
When program executes, if WAIT value is not 0.0, and SV reaches set temperature, as PV has not reached target
temperature, controller will wait for PV temperature to reach (target SV-WAIT)