12. Alarm Action
Description
The FY/FA series controller can support up to three sets of alarm functions. Each set of alarms has 19 mode.
Users can choose the most suitable alarm mode according to their needs for system protection or application.
Function Diagram
PV
SV
OUT1
%
0
20
40
60
80
100
200.0
SET
A/M
TAIE
FY900
OUT1
OUT2
AT
AL1
AL2
AL3
MAN
PRO
100.0
Alarm 1
Alarm 2
Alarm 3
Parameter
Parameter
Symbol
Content
Range
Default
Level
Hide/
Display
MAX
MIN
AL1
Alarm1 set value
9999
-1999
1.0
Level 1
SET1.3
AL2
Alarm2 set value
9999
-1999
1.0
Level 1
SET1.4
AL3
Alarm3 set value
9999
-1999
1.0
Level 1
SET2.1
ALD1
Alarm1 mode selection
(Please refer to Chapter 12.1 Alarm
Mode)
19
0
11
Level 3
SET3.1
ALT1
Alarm1 time setting
0
:
Flicker
99.59
:
Continued ON
0.01~99.58
:
delay time
Time format
:
min . sec
99.59
0.00
99.59
Level 3
SET3.2
ALD2
Alarm2 mode selection
(Please refer to Chapter 12.1 Alarm
Mode)
19
0
11
Level 3
SET3.3
ALT2
Alarm2 time setting
0
:
Flicker
99.59
:
Continued ON
0.01~99.58
:
delay time
Time format
:
min . sec
99.59
0.00
99.59
Level 3
SET3.4
ALD3
Alarm3 mode selection
(Please refer to Chapter 12.1 Alarm
Mode)
18
0
11
Level 3
SET4.1
ALT3
Alarm3 time setting
0
:
Flicker
99.59
:
Continued ON
0.01~99.58
:
delay time
Time format
:
min . sec
99.59
0.00
99.59
Level 3
SET4.2
HYSA
Hysteresis setting for alarm1~3
999.9
-199.9
1.0
Level 3
SET4.3
SETA
Alarm special function setting
(Please refer to Chapter 12.2)
1111
0000
0000
Level 3
SET5.3