FY operation manual 46
11.5 Dehumidification Function
Description
The FY/FA series controller provides dehumidification function to protect the heater. When the power is turned on, the heater is
dehumidified with low power. When the dehumidification is completed, the normal power is output to the heater.
Function Diagram
Time < RH.TM use RH.PO as manipulated output value
PV < RH.TC use RH.PO as manipulated output value
Time
MV(%)
100.0
RH.PO
RH.TM
Temperature
MV(%)
100.0
RH.PO
RH.TC
Parameter
Parameter
Symbol
Content
Range
Default
Level
Hide/
Display
MAX
MIN
RH.TC
Dehumidification temperature
If PV less than RHTC manipulated
value = RHPO
200.0
0.0
125.0
Fast
---
RH.PO
Dehumidification manipulated value
0 : OFF disable dehumidification
function
Other values : 0.1~100.0
manipulated value
100.0
OFF
OFF
Fast
---
RH.TM
Dehumidification time
time format : min.sec
COTI
0.00
15.00
Fast
---
Example
After the controller is turned on, when the PV does not reach 50°C, manipulated value fixed in 20%. When the time
exceeds 15 minutes or the PV is greater than 50°C, the controller will produce output of normal PID gain.
Parameter setting
Level
Parameter
Set value
Description
1
SV
100.0
Target temperature
Fast
RH.TC
50.0
Execute de-humidifying function when PV is
lower than this temperature
Fast
RH.PO
20.0
When executing dehumidification function
the manipulated value fixed in 20%
Fast
RH.TM
15.00
Max dehumidification function time
Содержание FY400
Страница 85: ...FY operation manual 84 MEMO...
Страница 86: ...85 FY operation manual MEMO...
Страница 87: ...FY operation manual 86 MEMO...
Страница 88: ...87 FY operation manual MEMO...