63
FY operation manual
13.1
Parameter
Parameter
Symbol
Content
Range
Default
Level
Hide/
Display
MAX
MIN
SV_4
Segment 4 SV
USPL
LSPL
0.0
Level 1
PROG=ON
TM_4
Segment 4 execute time setting
99.59
-1
0.00
Level 1
PROG=ON
OUT4
Segment 4 output limit
100.0
0.0
100.0
Level 1
PROG=ON
SV_5
Segment 5 SV
USPL
LSPL
0.0
Level 1
PROG=ON
TM_5
Segment 5 execute time setting
99.59
-1
0.00
Level 1
PROG=ON
OUT5
Segment 5 output limit
100.0
0.0
100.0
Level 1
PROG=ON
SV_6
Segment 6 SV
USPL
LSPL
0.0
Level 1
PROG=ON
TM_6
Segment 6 execute time setting
99.59
-1
0.00
Level 1
PROG=ON
OUT6
Segment 6 output limit
100.0
0.0
100.0
Level 1
PROG=ON
SV_7
Segment 7 SV
USPL
LSPL
0.0
Level 1
PROG=ON
TM_7
Segment 7 execute time setting
99.59
-1
0.00
Level 1
PROG=ON
OUT7
Segment 7 output limit
100.0
0.0
100.0
Level 1
PROG=ON
SV_8
Segment 8 SV
USPL
LSPL
0.0
Level 1
PROG=ON
TM_8
Segment 8 execute time setting
99.59
-1
0.00
Level 1
PROG=ON
OUT8
Segment 8 output limit
100.0
0.0
100.0
Level 1
PROG=ON
WAIT
Program execution standby
temperature
0 : when program execute do not
wait for PV temperature
Other values : when PV= (target SV-
WAIT), program entering next
segment
1000
0
0
Level 1
SET5.3
SET8.1
Program execute repeat
0 : disable repeat function
1 : Program execute repeat
1
0
0
Level 4
---
SET8.2
Program execute power fail
protection
0 : disable power fail protection
1 : enable power fail protection
1
0
0
Level 4
---
SET8.3
Program execute start address
0 : execute from zero
1 : execute from current PV
1
0
1
Level 4
---
SET9.2
Program time format
0 : hour.minute
1 : minute.second
1
0
0
Level 4
---
13.2 Key Operation Description
Functions
Keys
Description
Run
Eexecuting program, PRO_LED lamp ON, Upper area shows 3 times "RUN"
messages.
Halt
Pause executing program, PRO_LED lamp remains ON, at this moment upper area
will display current temperature value and
“HALT” message alternately.
Jump
+
Jump to the next segment, and it can skip segment continuously.
Holding UP key and press SET key 1 time to skip 1 segment, press SET key 2 times
to skip 2 segments, so on and so forth.
Reset
+
Stop executing program, PRO_LED lamp OFF, Upper area shows 3 times "REST"
messages.
PV/SV monitor
Press the A / M key for 2 seconds jump to the parameter OUTL, then pressing the
A / M key for 2 seconds return to PV / SV monitor.