FY operation manual 34
10.9 LEVEL_3 Parameter
Parameter
Symbol
Content
Range
Default
Hide/
Display
MAX
MIN
SETA
Alarm special function setting
(Please refer to Chapter 12.2)
1111
0000
0000
SET5.3
PSL
Protocol selection
0 : TAIE
1 : RTU
(Please refer to communication manual)
RTU
TAIE
RTU
SET5.4
BITS
Data format
0 : O_81
(parity bit=odd, stop bit=1)
1 : O_82
(parity bit=odd, stop bit=2)
2 : E_81
(parity bit=even, stop bit=1)
3 : E_82
(parity bit=even, stop bit=2)
4 : N_81
(parity bit=none, stop bit=1)
5 : N_82
(parity bit=none, stop bit=2)
N_82
O_81
O_81
SET5.4
IDNO
Controller station
254
0
1
SET5.4
BAUD
Baud rate
0 : 24(2400)
1 : 48(4800)
2 : 96(9600)
3 : 192(19200)
4 : 384(38400)
5 : 576(57600)
6 : 1152(115200) bps
1152
24
384
SET5.4
SVOS
SV bias
100.0
-100.0
0
SET6.1
PVOS
PV bias
PV = PV x (PVOH / 5000) + PVOS
199.9
-199.9
0
SET6.2
UNIT
Unit
Change this parameter USPL&LSPL
will be reset
0 : °C
1 : °F
2 : U (Linear signal)
2
0
---
SET6.3
PVFT
PV digital filter
The PV filter is used to eliminate noise
against the measured input
Unit : second
10.00
0.01
2.00
SET6.4
PV2
Use for motor valve feedback value
100.0
0.0
---
OUTY=2
&
SET7.1
OUD
Control action selection
0 : HEAT reverse action
1 : COOL direct action
COOL
HEAT
HEAT
SET7.2
OPAD
Super SV function, suppressing overshoot
0 : OFF
1 : ON
ON
OFF
OFF
SET7.3
HZ
Power frequency
0 : 50HZ
1 : 60HZ
50HZ
60HZ
60HZ
SET7.4