34 / 48 | PP-28_201612 | PKIR, PKIS
Electric
equipment
Type
of activation code
Electric parameters
PKIS3G and PKIR3G
PKIS-EI90S and PKIS-EI120S
Switches
Applies to all, except ZV DC 12/24 V, 3A; AC 125/250 V, 3A
DC 12/24 V, 3A; AC 125/250 V, 3A
M
agne
t
Impulse
DV5-2
AC 24 V, 50/60 Hz, 0,30 kVA, load factor 40% AC 24 V, 50/60 Hz, 240 VA, load factor 40%
DV6-2
AC 230 V, 50/60 Hz, 0,30 kVA, load factor 40% AC 230 V/50 Hz, 240 VA, load factor 40%
DV5C-2
DC 24 V, 31 W, load factor 40%
DC 24 V, 47 W, load factor 40 %
In
ter
-
rup
tion
DV5B-2
AC 24 V, 50/60 Hz, 4 W, load factor 100%
-
DV6B-2
AC 230 V, 50/60 Hz, 4 W, load factor 100%
AC 230 V, 50/60 Hz, 6 W, load factor 100 %
DV5D-2
DC 24 V, 4 W, load factor 100 %
DC 24 V, 4 W, load factor 100 %
Actuator
DV7-T
AC 230 V, 50/60 Hz, 7 VA
AC 230 V, 50/60 Hz, 10 VA
DV9-T, DV9-T-W
AC 24 V, 50/60 Hz, 7 VA; DC 24 V, 7 VA
AC 24 V, 50/60 Hz, 7 VA; DC 24 V, 10 VA
DV9-T-ST
AC 230 V, 50/60 Hz, 11 VA
AC 230 V, 50/60 Hz, 11 VA
DV9-T-SR
AC 24 V, 50/60 Hz, 7 VA; DC 24 V, 5 VA
AC 24 V, 50/60 Hz, 7 VA; DC 24 V, 9,5 VA
Tab. 27: Electric parameters of the microswitches, electromagnets and servomotors based on the type of activation mechanism
NOTE: Load factor: 40 % - maximum 120 s under voltage, 100 % - continuous load pressure.
BELIMO BLF230-T, BF230-T
Fig. 26: Servomotor connection scheme for DV7-T
Note
• Caution: Main power supply voltage!
• A device that disconnects the pole conductors
(minimum contact gap 3 mm) is required
for isolation from the power supply
• Parallel connection of several actuators possible
Power consumption must be observed!
S1 S2 S3 S4 S5 S6
<5°
<80°
2
1
N L1
BAE72B- S
Tf1
Tf2
Tf3 LE D
BELIMO BLF24-T, BF24-T
Fig. 27: Servomotor connection scheme for DV9-T
Note
• Supply via safety isolation transformer
• Parallel connection of several actuators possible
• Power consumption must be observed!
S1 S2 S3 S4 S5 S6
<5°
<80°
2
1
–
+
T
~
BAE72B-S
Tf1
Tf2
Tf3 LE D
S1 S2 S3 S4 S5 S6
<5°
<80°
BAE72B- S
Tf1
Tf2
Tf3 LED
Y
U
1
3
2
5
DC 0…10 V
DC 2…10 V
– +
T
~
Note:
• Supply via safety isolation transformer
• Parallel connection of several actuators possible
Power consumption must be observed!
BELIMO BF24-SR-T
Fig. 28: Electric servomotor connection scheme