7
Base setup
7.1
Programming of the desired function (Speed controller / P-Controller, PI-Controller)
•
It is possible to use the device as a Speed controller or as a P-controller, PI-Controller. Selection
of the function must
fi
rst be made by setting the internal jumper
“
E1
”
and dipswitch
“
S1
”
.
•
Factory setting of internal jumper
“
E1
”
in position for 0 - 10 V input signal.
When using
other signals bring the jumper in correct position.
•
Factory setting of all dipswitches is
|
OFF
|
position for operation as Speed controller
1.01
with external setting signal.
In the following the fundamental dipswitch positions for
further modes of operation are represented. Depending upon desired function further adjust-
ments are necessary (
function dipswitches).
Attention!
Setting of jumper and switches not under voltage! Observe the safety notices!
Changed functions become active partly only after renewed switching on the mains voltage!
E1 Analog In (factory setting 0 - 10 V)
13.03.2012
v_jumper_e1_dip_s1_mode.vsd
1
GND
0 - 10 V
10 k
1
GND
TF..
TF.. (KTY)
3
1
BN
GN
24V
1
MBG..
4 - 20 mA
(0 - 20 mA)
4 - 20 mA
24V
1
GND
YE
DSG..
WH
BN
0 -10 V
24V
1
GND
MAL1/10
2
1
0 -10 V
E1
E1
0 - 10 V
E1
0 - 10 V
E1
.01
.01
.01
.01
ON
OFF
10
9
8
7
6
5
4
3
2
1
S1
ON
OFF
10
9
8
7
6
5
4
3
2
1
S1
ON
OFF
10
9
8
7
6
5
4
3
2
1
S1
ON
OFF
10
9
8
7
6
5
4
3
2
1
S1
7.2
Select operation mode
Simple installation is possible through the use of modes of operation.
Mode
Signal or Sensor
(input)
Function
1.01
Signal 0 - 10 V
Speed controller, two step operation (factory setting)
2.01
Sensor TF.. (E1)
Temperature control airconditioning and refrigeration
3.01
Sensor MBG.. (E1)
Pressure control condensers (refrigeration)
4.01
Sensor DSG.. (E1)
Pressure control for ventilation systems
Sensor MAL.. (E1)
Air velocity control e.g. clean room
Operating Instructions
RETP6 / RETP10
Base setup
L-BAL-E082-GB 1237 Index 002
Part.-No. 00163339-GB
14/31