9.2
Temperaturre control (P-Controller)
2.01
9.2.1
Setting for operation as Temperature controller
%
set
0
100
R4
08.02.2008
v_set_pxet.VSD
potentiometer inside
(DIP 2 = OFF)
or
26.05.2008
v_pxet_q_aussen
_pot.VSD
potentiometer outside
(DIP 2 = ON)
set
Setpoint setting alternatively by
“
potentiometer inside
”
(DIP 2 =
|
OFF
|
) or
“
potenti-
ometer outside
”
(DIP 2 =
|
ON
|
)
For
control with active sensors (0 - 10 V, 4 - 20 mA)
Setting range: 0 - 100 %
measuring range of sensor
For
Temperature control with passive sensors TF.. (KTY)
Setting range: 0 - 100 %
-26...76
°
C (measuring range of controller)
The enclosed scale for type TF.. temperature sensors can be attached
above the potentiometer.
28.05.2008
v_pxet_q_skala_temp.VSD
set [% ]
0
10
20
30
40
50
60
70
80
90
100
[C°]
-26.0
-15.8
-5.6
4.6
14.8
25.0
35.2
45.4
55.6
65.8
76.0
Scale 0 - 100 % -26...76
°
C for Temperature control with passive sensors TF.. (KTY)
set
[%]
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
95 100
[
°
C] -26.0 -20.9 -15.8 -10.7 -5.6
-0.5
4.6
9.7 14.8 19.9 25.0 30.1 35.2 40.3 45.4 50.5 55.6 60.7 65.8 70.9 76.0
20.03.2008
v_pand_pxet.VSD
R5
%
Pband
5
30
Pband
Pband
Narrow control range = Short control times
Wide control range = Longer control times and more stable control
For
control with active sensors (0 - 10 V, 4 - 20 mA)
Setting range: 5 - 30 %
5 - 30 % measuring range of sensor
For
Temperature control with passive sensors TF.. (KTY)
Setting range: 5 - 30 %
5.1 - 30.6 K
08.02.2008
v_nmin_pxet.VSD
%
n-min
0
100
R6
n-min
Minimum output voltage (basic speed)
Setting range: 0 - 100 % (
“
n-min
”
takes priority if over
“
n-max
”
)
08.02.2008
v_nmax_pxet.VSD
%
n-max
0
100
R
7
n-max
Maximal output voltage (speed limiter)
Setting range: 100 % -
“
n-min
”
Operating Instructions
RETP6 / RETP10
Setting for operation
L-BAL-E082-GB 1237 Index 002
Part.-No. 00163339-GB