9.3.2
Example Pressure control condensers
Pressure sensor
•
Type MBG-30I
•
Measuring range 0 - 30 bar
•
Output signal 4...20 mA
Settings:
•
set
= 50 % 15.0 bar, in use of refrigerant medium table for R507
•
Pband
= 10 % 3.0 bar
U
Motor
50 %
100 %
[bar] / [°C]
50 %
15 bar ^ 34.28 °C @
507
Set
Pband
10 %
12.03.2008
v_diagramm_bar_c.vsd
18 bar ^ 41.53 °C @ 507
n-min. 0 %, n-max. = 100 %
n-min. 35 %, n-max. = 85 %
Idealized principle diagram
Operating Instructions
RETP6 / RETP10
Setting for operation
L-BAL-E082-GB 1237 Index 002
Part.-No. 00163339-GB
22/31