SY120SA Series Operating Manual
© 2004 by SYRIS Technology Corp.
8
2.8.8
Restore Default setting
(including Master card, parameter,card and record)
1. Enter[FUN][4][9][EN],if correct and will response correct status.
2. Enter again[FUN][4][9][EN]
Æ
wait 5 seconds to clean all setting. System will restore all.
2.9
Configure System parameter
[needs to be in the login status]
2.9.1
Card number with password or password only
1. Enter[FUN][5][1](P)[EN]
(P):P = 1 use card number and password(default);
P = 0 password enter
2.9.2
Change user default password(
default = 0000
)
1. Enter[FUN][5][2](nnnn)(nnnn)[EN]
(nnnn)(nnnn):new password need enter 2 times to confirm.
2.9.3
Error psaaword keylock setting
1. Enter[FUN][5][3](K)(L)(A)[EN]
(K):setting acceptable error times,range:1~9;default :6
(L):enter lock time setting,range:1~9,unit: min;default :3
(A):enter lock time and show alarm setting status;
A = 1 start,
A = 0 close(default)
2.9.4
Activate guard and indicate source, delay time
1. Enter[FUN][5][4](R)(TT)[EN]
(R):R = 0 set inside delay,time us TT to set.It’s default
R = 1 seting inport enter,please follow:system inport setting function
(TT): Activate guard delay time setting, Range:01~99; default :05,unit:sec
2.9.5
Setting alarm enabled
1. Enter[FUN][5][5](B)[EN]
(B):B = 0 close alarm voice output,
B = 1 allow alarm voice output(default)
2.9.6
Setting doorbell enabled
1. Enter[FUN][5][6](B)[EN]
(B):B = 0 close doorbell voice output,
B = 1 allow doorbell voice output(default)
2.9.7
Configure Extern Module
(V2.0)
1. Enter[FUN][5][7](E)[EN]
(E):E = 0 no extern module(default)
E = 1 use extern module