background image

 

SY120SA Series Operating Manual                                                             

 

© 2004 by SYRIS Technology Corp.   

                 

                                                                               

10

 

Output contact purpose code list   

Code Purpose 

Remark 

0 Don’t 

use 

 

open control 

(E-lock output  point  default) 

Doorbell contact output 

(relay output point default ) 

Guard system set output   

Control and remove guard 

Alarm contact output 

Use remove guard to cancel alarm 

Anti-duress contact  output 

Use[FUN][4][4]to cancel anti-duress 

※ 

Action time if set 0 and will action until remove. 

 
 

2.12      System    group & timezone control function 

[needs to be in the login status]

 

2.12.1  Configure system time 

1. Enter[FUN][8][1](YYYY)(MM)(DD)(hh)(mm)(ss)[EN] 

(YYYY):year,Range :2000~2199.(MM):month,Range 01~12. 

(DD):day,Range 01~31 

(hh):hour,Range 00~23. (mm):min,Range 00~59.   

(ss):sec,Range 00~59 

2.12.2  Configure timezone 

1. Enter[FUN][8][2](HHMM)(hhmm)[EN] 

(HHMM):Set start time; 

HH = hour , MM = minute;    default:    0700 

(hhmm):setting timezone end ; 

hh = hour;   mm = minute;   default:  1900 

2.12.3   Setting group timezone 

1. Enter[FUN][8][3](G)(D)(N)(A)[EN] 

(G):group code(1 to 4) 

(D):on timezone ( 0 to 3) 

(N):out of timezone (0 to 3) 

Timezone function code list:

0:stop enter 

2:card(system default) 

 

1:card or password 

3:card+password 

(A):pass dooe area,1 = enable [EN] (default),0 = disable [EN]; 

2.12.4   Group weekly schedule 

1. Enter[FUN][8][4](G)(WWWWWWW)(H)[EN] 

(WWWWWWW):week schedule, from Sunday to saturday, 

1 = Enable enter(default),0 = Disable enter; 

(G):Group No; Range1~4 

(H):Holiday control,1 = can enter(default),0 = can’t enter; 

 

 

 

Содержание SY120SA

Страница 1: ...SY120SA Series Operating Manual Version 3 0 2004 by SYRIS Technology Corp ...

Страница 2: ...cess and many other use which could be able to apply on SY120SA The build in functions also includes two section s anti theft and emergency control which can work with alarm system for arm and disarm In SY120SA s System Setting Function Table shows all of the functions For more detail please check the following instructions User can use all of the control setting form the reader s kekpad The follo...

Страница 3: ...sword 57 Setup extend module 91 Setup controller ID Please see the reader display list for more particular system light description 1 2 Reader LED status list Show light sound Footnote code Status description OK LED SY120SA Power LED SY120SA Error LED error BEEPER voice 0 Normal status off LED Red LED Orange no action 1 Correct status LED Green LED Red off short beep 0 5sec Return to original stat...

Страница 4: ...ct anti anti duress on the controller will show correct LED message and will open the door automatically If anti druess mode had been activated the controller will has anti duress action at same time 3 If invalid card or wrong password and system will response error message 2 2 Access without Prox card 2 2 1 Access with card s password or card number and card password 1 Enter pppp EN system will c...

Страница 5: ...twice Password enter mode 1 Follow the sequence of NNNN pppp nnnn nnnn EN wait for confirmation from controller if correct then the old password will be changed to new one and show correct message NNNN Valid card number The range are in between 0001 2000 pppp Previus password or system original passowrd Defualt 0000 nnnn nnnn new password needs to be entered twice 2 4 Method of Deactivate alarm 1 ...

Страница 6: ...UN Æ 2 Æ EN in logout status and wait for system response 2 If Master card and system into waiting response proximity card status correct or no setting card andneed to into the next step 3 System enter waiting password enter status waiting to enter setting card password 4 If correct and login directly If use setting card and need to use card and password default setting card password 1234 2 6 2 Lo...

Страница 7: ...l add card and press EN to exit NNNN add card group start number Range 0001 2000 G add card group code Range 1 4 Add card number will be start and response step by step until 2000 After add card and will be seeting in the same group code 2 7 6 Delete multiple cards 1 Enter FUN 3 6 NNNN EEEE EN NNNN start delete group card number Range 0001 2000 EEEE the end of delete group card number Range 0001 2...

Страница 8: ...3 if use any setting card 1 3 the other card password need to operate with setting card password 2 8 3 Settup anti duress password 1 Enter FUN 4 3 N pppp EN N anti duress group Range 1 4 pppp enter anti duress password System default value is 1 4 units all is 5555 If personal passowrd is the same as anti duress password It can be personal password 2 8 4 Enabled or Disable anti duress 1 Enter FUN 4...

Страница 9: ...lock setting 1 Enter FUN 5 3 K L A EN K setting acceptable error times range 1 9 default 6 L enter lock time setting range 1 9 unit min default 3 A enter lock time and show alarm setting status A 1 start A 0 close default 2 9 4 Activate guard and indicate source delay time 1 Enter FUN 5 4 R TT EN R R 0 set inside delay time us TT to set It s default R 1 seting inport enter please follow system inp...

Страница 10: ...lose NC Input point function code list Code Purpose Remark 0 Don t use 1 Door sensor DI1 default 2 Open switch DI2 default 3 Emergent open switch Start door area and send alarm until remove 4 Detect guard setting status Detect setting guard or not 5 Doorbell enter CALL keypad default 6 Emergent help switch Send alarm until remove 7 First area alarm detect Send alarm until remove spread status 8 Se...

Страница 11: ...mm ss EN YYYY year Range 2000 2199 MM month Range 01 12 DD day Range 01 31 hh hour Range 00 23 mm min Range 00 59 ss sec Range 00 59 2 12 2 Configure timezone 1 Enter FUN 8 2 HHMM hhmm EN HHMM Set start time HH hour MM minute default 0700 hhmm setting timezone end hh hour mm minute default 1900 2 12 3 Setting group timezone 1 Enter FUN 8 3 G D N A EN G group code 1 to 4 D on timezone 0 to 3 N out ...

Страница 12: ...e needs to change 3 cards at same time if one uses Master card to login then system will make it itÆAccess with Master card s passwrod as invalid 2 SY120SA controller system and reader needs to be connected the GND Please use parallel cable while using parallel cable with 0 75mm shield cover cable it can connect up to 100 meter long While useing normal phone line the distance limits is within 20 m...

Страница 13: ...SY120SA Series Operating Manual 2004 by SYRIS Technology Corp 12 ...

Отзывы: