Object Name:
upsInputFrequency
OID: u
psObjects.3.3.1.2
Type:
Non-negative
Integer
Access:
Read-Only
Object returns the measured frequency from this input source in tenths of Hertz.
Object Name:
upsInputVoltage
OID:
upsObjects.3.3.1.3
Type:
Non-negative Integer
Access:
Read-Only
Object returns the measured input voltage of this source. AC input sources return the RMS line-to-line
input voltage in units of Volts.
Object Name:
upsInputCurrent
OID:
upsObjects.3.3.1.4
Type:
Non-negative Integer
Access:
Read-Only
Object returns the measured input current of an AC input in units of tenths of Amps RMS.
Object Name:
upsInputTruePower
OID:
upsObjects.3.3.1.5
Type:
Non-negative Integer
Access:
Read-Only
Object returns the measured true input power an AC input in units of Watts.
4.1.3
upsOutput Group
Object Name:
upsOutputSource
OID:
upsObjects.4.1
Type:
Integer, {other=1, none=2, normal=3, bypass=4, booster=6, reducer=7}
Access:
Read-Only
Object returns the present source of output power. If the output is not presently on, the value returned
will be 2 (none). If the output is enabled, the value returned will be 3 (normal). The other enumeration
values are unused by the SynQor Agent.
Object Name:
upsOutputNumLines
OID:
upsObjects.4.3
Type:
Non-negative Integer
Access:
Read-Only
Object returns the number of outputs installed in the MPS device.