Object Name:
upsIdentAgentSoftwareVersion
OID:
upsObjects.1.4
Type:
String
Access:
Read-Only
Object returns the SynQor assigned code revision of the communications card implementing the
network interface.
Object Name:
upsIdentName
OID:
upsObjects.1.5
Type:
String
Access:
Read-Write
This field is a user assignable name available to identify this device. Default value is blank.
Object Name:
upsIdentAttachedDevices
OID:
upsObjects.1.6
Type:
String
Access:
Read-Write
This field is a user assignable string available to identify this device. Default value is blank.
4.1.2
upsInput Group
Object Name:
upsInputLineBads
OID:
upsObjects.3.1
Type:
Counter32
Access:
Read-Only
Object returns the count of times an input voltage transitions from good to bad.
Object Name:
upsInputNumLines
OID:
upsObjects.3.2
Type:
Non-negative Integer
Access:
Read-Only
Object reports the number of inputs installed on this MPS. This will return “4” – there is one input listed
for each AC line-to-line phase, and a fourth entry which provides the aggregated power of the three
phases.
4.1.2.1
upsInputTable
The
upsInputTable
object (upsObjects.3.3) contains a single entry for each input installed in the device,
and a fourth entry for the combined total. The fourth (aggregated) entry contains only the total
measured input power. Each entry contains up to four fields, as listed here.
Содержание MPPS-4000-1U
Страница 7: ...Figure C Control Page in Web Interface...