Object Name:
upsTestResultsSummary
OID:
upsObjects.7.3
Type:
Integer, {done/pass=1, done/warning=2, done/error=3, aborted=4, in progress=5, no test
initiated=6}
Access:
Read-Only
This object returns a summary of the result of a previously initiated self-test routine.
Object Name:
upsTestResultsDetail
OID:
upsObjects.7.4
Type:
String
Access:
Read-Only
Value of this object is a string describing the result of the last self-test routine. If the test ended with an
error or warning, the string will describe the error or warning.
Object Name:
upsTestStartTime
OID:
upsObjects.7.5
Type:
Timestamp
Access:
Read-Only
Object returns the value of the
sysUpTime
object (1.3.6.1.2.1.1.3) at the time the previous self-test was
initiated.
Object Name:
upsTestElapsedTime
OID:
upsObjects.7.6
Type:
Time-interval
Access:
Read-Only
Object returns the elapsed running time of the previous self-test.
4.1.7
upsControl Group
Object Name:
upsShutdownType
OID:
upsObjects.8.1
Type:
Integer, {output = 1, system = 2}
Access:
Read-Only
For the SynQor MPS, all commanded shutdowns disable the output, and do not power-down the MPS
hardware. This object will always return a value of 1, indicating output-shutdown.
Object Name:
upsShutdownAfterDelay
OID:
upsObjects.8.2
Type:
Integer
Access:
Read-write
Содержание MPPS-4000-1U