A write to this object will initiate a shutdown of the MPS output after the designated number of
seconds. A write of the value 0 will cause the MPS output to shut down immediately. A write of -1 will
abort a pending shutdown.
Object Name:
upsStartupAfterDelay
OID:
upsObjects.8.3
Type:
Integer
Access:
Read-write
A write to this object will initiate a startup of the MPS output after the designated number of seconds.
A subsequent write of -1 will abort the timer. A write of the value 0 will cause the MPS output to start
immediately.
Object Name:
upsRebootWithDuration
OID:
upsObjects.8.4
Type:
Integer
Access:
Read-write
The Reboot with Duration feature will automatically disable the MPS output for a period indicated by
the number of seconds from upsShutdownType, after which time, the MPS output will be enabled.
Object Name:
upsAutoRestart
OID:
upsObjects.8.5
Type:
Integer, {on=1, off=2}
Access:
Read-write
The auto-restart feature will automatically enable the MPS output when the device receives input
power from a powered-off state. This feature is disabled by default. A write of the value 1 to this object
will enable the auto-restart feature. The setting is stored in non-volatile memory.
4.1.8
upsConfig Group
Object Name:
upsConfigInputVoltage
OID:
upsObjects.9.1
Type:
Non-negative Integer
Access:
Read-Only
Object returns the nominal designed input voltage of the device. The SynQor MPS is a universal input
device (115 / 230 V) and this object will always return the value 115.
Object Name:
upsConfigInputFreq
OID:
upsObjects.9.2
Type:
Non-negative Integer
Access:
Read-Only
Object returns the nominal designed input frequency of the device. This object will always return the
value 600, representing 60 Hz.