A write to this object will initiate a shutdown of the MPS output after the designated number of 
seconds.  A write of the value 0 will cause the MPS output to shut down immediately.  A write of -1 will 
abort a pending shutdown. 

Object Name: 

upsStartupAfterDelay 

OID: 

upsObjects.8.3 

Type: 

Integer 

Access: 

Read-write 

A write to this object will initiate a startup of the MPS output after the designated number of seconds.  
A subsequent write of -1 will abort the timer.  A write of the value 0 will cause the MPS output to start 
immediately. 

 

Object Name: 

upsRebootWithDuration 

OID: 

upsObjects.8.4 

Type: 

Integer 

Access: 

Read-write 

The Reboot with Duration feature will automatically disable the MPS output for a period indicated by 
the number of seconds from upsShutdownType, after which time, the MPS output will be enabled. 

 

Object Name: 

upsAutoRestart 

OID: 

upsObjects.8.5 

Type: 

Integer, {on=1, off=2} 

Access: 

Read-write 

The auto-restart feature will automatically enable the MPS output when the device receives input 
power from a powered-off state.  This feature is disabled by default.  A write of the value 1 to this object 
will enable the auto-restart feature.  The setting is stored in non-volatile memory. 

4.1.8

 

upsConfig Group 

Object Name: 

upsConfigInputVoltage 

OID: 

upsObjects.9.1 

Type: 

Non-negative Integer 

Access: 

Read-Only 

Object returns the nominal designed input voltage of the device.  The SynQor MPS is a universal input 
device (115 / 230 V) and this object will always return the value 115. 

Object Name: 

upsConfigInputFreq 

OID: 

upsObjects.9.2 

Type: 

Non-negative Integer 

Access: 

Read-Only 

Object returns the nominal designed input frequency of the device.  This object will always return the 
value 600, representing 60 Hz. 

Содержание MPPS-4000-1U

Страница 1: ...PS 4000 1U 1 888 567 9596 USA only SynQor Headquarters 155 Swanson Road Boxborough MA 01719 1316 USA www synqor com Made in USA Military Power SuPPly Operator s Guide Ethernet SNMP QMS 006 0006748 Rev...

Страница 2: ...ration 2 2 1 DHCP Server 2 2 2 NetBIOS Hostname 2 2 3 Local Connection 2 3 Web Interface 3 3 1 MONITOR Page 4 3 2 CONTROL Page 5 3 3 NETWORK Page 7 3 4 ALERTS Page 9 3 5 SNMP Page 10 3 6 DEBUG Page 13...

Страница 3: ...elow Once a DHCP server assigns an IP address to the MPS the web interface can be loaded by pointing a web browser to the address http x x x x where x x x x is the assigned IP address 2 2 NetBIOS Host...

Страница 4: ...to mark the MPS Certificate as a trusted certificate Note that the certificate includes the NetBIOS name as the common name as part of its verification criteria so the certificate is rebuilt after a...

Страница 5: ...pecified This page gives an overview of monitored parameters and configuration The items that are displayed vary based on the installed options For example if the MPS does not have the auxiliary DC ou...

Страница 6: ...e output after a designated off time Set the unit to shut down the output after a designated delay Set the unit to enable the output after a designated delay Abort a pending startup or shutdown delay...

Страница 7: ...Figure C Control Page in Web Interface...

Страница 8: ...interface via an SSL https connection 3 3 2 ADDRESS RESOLUTION DHCP is a protocol which allows the router to assign an IP address to a device on the network By default DHCP is enabled and the MPS will...

Страница 9: ...ce for a single browser session the browser will retain the username and password and resend it with each additional request in the session In order to protect the password an SSL connection is requir...

Страница 10: ...e via the domain of the email user selected Select any items from the list of alarm conditions desired to initiate an email transmission Alert configuration is stored in non volatile memory after the...

Страница 11: ...Configuration Pane see Figure G All changes on this page are stored in non volatile memory when the appropriate Apply button is pressed Figure G SNMP Configuration Pane 3 5 1 Communities SNMPv1 and SN...

Страница 12: ...be set for the System MIB objects and the UPS MIB objects The System MIB objects reference network parameters such as access errors device up time and network identification variables The UPS MIB obje...

Страница 13: ...raps can be sent either via the SNMPv2 message format or the SNMPv3 message format SNMPv2 traps have their own community that must be recognized by the receiver Enter a community name recognized by th...

Страница 14: ...e debug page provides a scrollable mirror of the RS232 serial interface The user can also transmit virtual serial commands by entering the commands and clicking the Send button Note that the debug htm...

Страница 15: ...r the RFC 1628 specification SNMPv3 messages use the same format as SNMPv2 messages with the addition of authentication and encryption 4 1 SNMP Exposed Objects In the following list of objects exposed...

Страница 16: ...ut Group Object Name upsInputLineBads OID upsObjects 3 1 Type Counter32 Access Read Only Object returns the count of times an input voltage transitions from good to bad Object Name upsInputNumLines OI...

Страница 17: ...ut in units of tenths of Amps RMS Object Name upsInputTruePower OID upsObjects 3 3 1 5 Type Non negative Integer Access Read Only Object returns the measured true input power an AC input in units of W...

Страница 18: ...f Amps Object Name upsOutputPower OID upsObjects 4 4 1 4 Type Non negative Integer Access Read Only Object returns the output voltage of the corresponding MPS output in units of Watts Object Name upsO...

Страница 19: ...OID of the desired test sequence is written to upsTestId The value written to upsTestSpinLock must be the present value read from upsTestSpinLock The spin lock provides a semaphore allowing only one...

Страница 20: ...t Name upsTestStartTime OID upsObjects 7 5 Type Timestamp Access Read Only Object returns the value of the sysUpTime object 1 3 6 1 2 1 1 3 at the time the previous self test was initiated Object Name...

Страница 21: ...ShutdownType after which time the MPS output will be enabled Object Name upsAutoRestart OID upsObjects 8 5 Type Integer on 1 off 2 Access Read write The auto restart feature will automatically enable...

Страница 22: ...always returns disabled because the MPS has no audible alarm output Object Name upsConfigLowVoltageTransferPoint OID upsObjects 9 9 Type Non negative Integer Access Read Only Object returns the value...

Страница 23: ...Name sysName OID 1 3 6 1 2 1 1 5 Type String Access Read Write Object provides a user settable string to enter an identifier for this device The value returned by this object is identical to that ret...

Страница 24: ...SNMPv3 message authentication Message authentication requires messages include the proper snmpEngineBoots parameter from the target device to prevent message replay attacks This object is only access...

Страница 25: ...table One exception is that there is no notification for the upsAlarmTestInProgress alarms The trap data includes the index of the new entry and the OID of the alarm description 4 2 3 upsTrapAlarmEntr...

Страница 26: ...1 888 567 9596 USA only SynQor Headquarters 155 Swanson Road Boxborough MA 01719 1316 USA www synqor com Made in USA Military Power SuPPly Operator s Guide Ethernet SNMP...

Отзывы: