4.1.3.1
upsOutputTable
The
upsOutputTable
object (upsObjects.4.4) contains an entry for each output installed in the MPS
device. Each output contains up to four fields, as listed here.
Object Name:
upsOutputVoltage
OID:
upsObjects.4.4.1.2
Type:
Non-negative Integer
Access:
Read-Only
Object returns the output voltage of the corresponding MPS output in units of Volts.
Object Name:
upsOutputCurrent
OID:
upsObjects.4.4.1.3
Type:
Non-negative Integer
Access:
Read-Only
Object returns the output current of the corresponding MPS output in units of tenths of Amps.
Object Name:
upsOutputPower
OID:
upsObjects.4.4.1.4
Type:
Non-negative Integer
Access:
Read-Only
Object returns the output voltage of the corresponding MPS output in units of Watts.
Object Name:
upsOutputPercentLoad
OID:
upsObjects.4.4.1.5
Type:
Non-negative Integer
Access:
Read-Only
Object returns the output voltage of the corresponding MPS output as a percentage of the rated output
power of the device.
4.1.4
upsBypass Group
The
upsBypass
group is not implemented by the SynQor MPS SNMP Agent because the MPS models do
not contain internal bypass devices.
4.1.5
upsAlarm Group
Object Name:
upsAlarmsPresent
OID:
upsObjects.6.1
Type:
Non-negative Integer
Access:
Read-Only
Object returns the total number of active alarms in the mpsAlarmsTable.
Содержание MPPS-4000-1U