Chapter 7 Specifications of the TimeProvider
Alarms
200
TimeProvider User’s Guide
097-58001-02 Revision G – April 2008
Alarms
Input Alarms
The PRS input is inhibited when a contact closure (less than 1
Ω
) is present across
the PRS Alarm In connection.
Output Alarms
The output alarm connector is on the Input module, and can be either a DB25
connector or wire-wrap pins. See
Making Alarm Connections
, on page 70
,
for a
pinout diagram of the DB-25 connector.
Table 7-6
describes the contact closure for
the alarm outputs.
Power
Dual power supplies from –36 to –72 V DC.
Table 7-7
lists the maximum and typical
power consumption using crystal and Rubidium IOCs.
Symmetricom recommends a 5 A fuse for the power supply to the TimeProvider
shelf.
Table 7-6. Output Alarm Specifications
Alarm
Description
Minor
Contact closure (NC or NO) 1 Amp Form C
Major
Contact closure (NC or NO) 1 Amp Form C
Critical
Contact closure (NC or NO) 1 Amp Form C
Table 7-7. Typical Power Consumption
IOC Type
Max Power (W)
per IOC
Typical Power (W)
per IOC
Crystal
40
30
Rubidium
60
40
(70 with two Rb IOCs)