Chapter 4 Provisioning the TimeProvider
Provisioning Alarms
128
TimeProvider User’s Guide
097-58001-02 Revision G – April 2008
CLKWARM
Local oscillator on the
specified IOC is in
Warm-up mode
MN | MJ
IMMED
No
MN
MN
CLKFREE
Local oscillator on
specified IOC is in
Free-run mode
MN | MJ |
CR
IMMED
No
MJ
MJ
CLKBRDG
Local oscillator on
specified IOC is in
Bridging mode
MN | MJ |
CR
IMMED
No
MJ
MJ
CLKHOLD
Local oscillator on
specified IOC is in
Holdover mode
MN | MJ |
CR
IMMED
No
MJ
MJ
<aid> = PRS
INPDISQ
Specified input has
been disqualified or
qualified as a possible
system reference.
MN | MJ |
CR
FLT
DELAY
Yes
MN
MN
INPLOS
Specified input has
Loss Of Signal.
1
MN | MJ |
CR
IMMED
No
MN
MN
INPFRQ
Specified input has
calculated received
frequency that exceeds
the pull-in range of the
LO.This alarm condition
disqualifies the input as
a possible reference.
2
NR | NA |
MN | MJ |
CR
IMMED
No
MN
NR
INPPHASE
Specified input port’s
phase measurement
exceeds usable value.
NR | NA |
MN | MJ |
CR
IMMED
No
MN
MN
EXDSC
Input has had excessive
discontinuities, indicated
by more than 3 signal
faults (OOF, BPV, CRC,
or AIS) within a 5-minute
window. The alarm
clears when the
5-minute window
contains less than 3
signal faults.
NR | NA |
MN | MJ |
CR
IMMED
No
MN
MN
Table 4-3. Alarm Conditions and Defaults (Continued)
Alarm ID
Description of Alarm
Condition
Possible
Alarm
Levels
Error
Delay
Default
Error
Delay
Editable?
Default Level
SSU
Mode
SUB
Mode
Содержание EDGE CLOCK 1000
Страница 1: ...TimeProvider 1000 and 1100 Edge Clock User s Guide Revision G April 2008 Part Number 097 58001 02 ...
Страница 10: ...Table of Contents 10 TimeProvider User s Guide 097 58001 02 Revision G April 2008 ...
Страница 154: ...Chapter 5 Testing the TimeProvider Test Record 154 TimeProvider User s Guide 097 58001 02 Revision G April 2008 ...
Страница 224: ...Index Y Y 224 TimeProvider User s Guide 097 58001 02 Revision G April 2008 ...