Chapter 6 Maintaining and Troubleshooting the TimeProvider
Diagnosing the IMC
162
TimeProvider User’s Guide
097-58001-02 Revision G – April 2008
4. Retrieve the contents of the IOC memory stored in the IMC by issuing the
following command.
CPY-MEM:::::IMC,IOC,IOC;
This command may take more than two seconds to execute; if it does, then the
In-Process response is issued. See the
TimeProvider TL1 Reference Guide
for
more information on the CPY-MEM command.
If you have not stored the contents of the IOC memory in the IMC, then provision
the IOC using the procedures and commands described in
Chapter 4,
Provisioning the TimeProvider
.
5. Issue the following TL1 command to place the IOC in service:
ED-EQPT::IOC1:::IOCSTATE=INSRV;
6. Install the IOC into the right slot of the shelf and tighten the captive retaining
screws. This IOC will become the Standby IOC.
7. Wait for the IOC to reboot and qualify the reference inputs. During this time the
Active IOC updates the new IOC’s memory with current values.
8. Issue the following TL1 command to place the Standby IOC in service:
ED-EQPT::IOC2:::IOCSTATE=INSRV;
Diagnosing the IMC
Reading LED Conditions
Table 6-3
shows the function of the LED indicators on the front panel of the IMC and
IMC/TPIU.
Table 6-3. LED Conditions for the IMC and IMC/TPIU
LED Name
Condition
Description
Power
Green
Off
Power is On
Power is Off
Fail
Red
Off
Card failure
No failure
Alarm
Red
Off
Card alarm
No alarm
Critical
Red
Off
Critical system alarm
No alarm
Содержание EDGE CLOCK 1000
Страница 1: ...TimeProvider 1000 and 1100 Edge Clock User s Guide Revision G April 2008 Part Number 097 58001 02 ...
Страница 10: ...Table of Contents 10 TimeProvider User s Guide 097 58001 02 Revision G April 2008 ...
Страница 154: ...Chapter 5 Testing the TimeProvider Test Record 154 TimeProvider User s Guide 097 58001 02 Revision G April 2008 ...
Страница 224: ...Index Y Y 224 TimeProvider User s Guide 097 58001 02 Revision G April 2008 ...