92
A-96.250.581 / 220616
AMI Codes-II CC
Program List and Explanations
5.3.2.32.31.3
Reset time:
The reset time is the time till the step response of a sin-
gle I-controller will reach the same value as it will be suddenly
reached by a P-controller.
Range: 0–9’000 Sec
5.3.2.32.31.4
Derivative time:
The derivative time is the time till the ramp re-
sponse of a single P-controller will reach the same value as it will
be suddenly reached by a D-controller.
Range: 0–9’000 Sec
5.3.2.32.31.5
Control timeout:
If a controller action (dosing intensity) is constantly
over 90% during a defined period of time and the process value
does not come closer to the setpoint, the dosing process will be
stopped for safety reasons.
Range: 0–720 min