100
A-96.250.581 / 220616
AMI Codes-II CC
Program List and Explanations
5.3.2.32.4
Control Parameters
Range for each Parameter same as
The relay will be active repetitively depending on the programmed
time scheme.
5.3.2.24
Mode:
Operating mode (interval, daily, weekly)
5.3.2.340
Interval:
The interval can be programmed within a range
of 1–1’440 min.
5.3.2.44
Run Time
: Enter the time the relay stays active.
Range: 5–32’400 Sec.
5.3.2.54
Delay
: during run time plus the delay time the signal and control
outputs are held in the operating mode programmed below.
Range: 0–6’000 Sec.
5.3.2.6
Signal Outputs
: Select operating mode of the signal output:
5.3.2.7
Output/Control
: Select operating mode of the controller output:
5.3.2.1
Function = Timer:
5.3.2.24
Interval
Cont.:
Signal outputs continue to issue the measured value.
Hold:
Signal outputs hold the last valid measured value.
Measurement is interrupted. Errors, except fatal errors,
are not issued.
Off:
Signal outputs are switched off (set to 0 or 4 mA).
Errors, except fatal errors, are not issued.
Cont.:
Controller continues normally.
Hold:
Controller continues based on the last valid value.
Off:
Controller is switched off.