2
measurement
Display
refresh
cycle
1 second
Setting mode
The panel touch button is set; The parameter’s setting value is locked in
password; The setting value is cut off for permanent storage.
Display mode
With 7 inch 800*480 dot matrix wide screen and TFT high brightness color
graphics LCD display, LED backlight, clear screen, wide viewing angle.
The display content can be composed of Chinese characters, numbers,
process curves, bar charts, etc. Through panel keys, the screen can be paged
up and down, the search of historical data before and after, the change of
curve time scale, etc.
Data backup
Support Flash and SD card for data backup and transfer, with the maximum
capacity of 8GB, supporting FAT, FAT32 format.
The memory capacity of internal Flash: 64M Byte
Recording interval 1, 2, 4, 6, 15, 30, 60, 120, 240 seconds ,totally 9 gears, are available for
selection.
Memory length
(UPS Continuous
recording)
24 days (while the interval is 1 second)—5825 days (while the interval is
240 seconds)
Formula: Recording duration(day)=
64×1024×1024×Recording interval(s)
No of channels×2×24×3600
(! Note: Calculation of the number of channels: The program divides the
number of channels into 5 gears ,that is, 4, 8, 16. When the number of
instrumentation channels falls between the two gears, the larger number is
used as the number of channels. For example, the number of instrument
channels is 12-channel, and the number of channels is calculated with 16 in
the formula.
Operating
environment
Ambient temperature:-10
~
50
℃
Relative humidity
:
10 ~ 90%RH (RH); avoid strong corrosive gases.
(! Note: In case the site is in bad condition, special instructions must be made
when ordering.
supply
AC85 to 264V (switching power supply), 50/60Hz
Power
Consumption
≤15W
Ⅲ
. Precautions for use and installation
3.1 Precautions for use
3.1.1 Precautions for use of this instrument
●There are more plastic parts for this instrument. When you clean it, please use a dry soft