22
4.12.4 Input configuration
★
Configuration channel: Select the number of channel for display configuration.
★
Bit number: It indicates the bit number of the engineering corresponding to the display
channel. As for the setting method, please refer to Section 4.12.4.1 Introduction to Input Method.
★
Signal types: B, S, K, E, T, J, R, N, F2, Wre3-25, Wre5-26, Cu50, Cu53, Cu100, Pt100,
BA1, BA2, 0
~
400Ω, 0
~
20mV, 0
~
100mV, ±20mV, ±100mV, 0
~
20mA, 0
~
10 mA, 4
~
20mA, 0
~
5V, 1
~
5V, √0
~
10mA, √4
~
20mA, √0
~
5V, √1
~
5V, nil.
The permitted ranges of all signals are stated as follows:
Signal
model
Scope of
range
Signal model
Scope of
range
Signal model
Scope of
range
B
400
~
1800
℃
Cu50
-50.0
~
150.0
℃
0
~
20mA
-9999
~
99999
S
-50
~
1600
℃
Cu53
-50.0
~
150.0
℃
0
~
10mA
-9999
~
99999
K
-200
~
1300
℃
Cu100
-50.0
~
150.0
℃
4
~
20mA
-9999
~
99999
E
-200
~
1000
℃
Pt100
-200.0
~
650.0
℃
0
~
5V
-9999
~
99999
T
-200.0
~
400.0
℃
BA1
-200.0
~
600.0
℃
1
~
5V
-9999
~
99999
J
-200
~
1200
℃
BA2
-200.0
~
600.0
℃
reserve
R
-50
~
1600
℃
0
~
400Ω Linear
resistance
-9999
~
99999
reserve
N
-200
~
1300
℃
0
~
20mV
-9999
~
99999
0
~
10mA
radication
F2
700
~
2000
℃
0
~
100mV
-9999
~
0
~
20mA