NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

5

COLD CLIMATE INSULATION

For cold climate installations, seal all cracks 

around your appliance with noncombustible 

material and wherever cold air could enter 

the room. It is especially important to insulate 

outside chase cavity between studs and under 

floor on which appliance rests, if floor is above 

ground level. Gas line holes and other open

-

ings should be caulked or stuffed with unfaced 

fiberglass insulation. 

If the fireplace is being installed on a cement 

slab in cold climates, a sheet of plywood or 

other raised platform can be placed underneath 

to  prevent  cold  transfer  to  the  fireplace  and 

into the room. It also helps to sheetrock inside 

surfaces and tape for maximum air tightness 

and caulk firestops.

MANUFACTURED hOME 
REQUIREMENTS

This appliance may be installed in an aftermar-

ket permanently located, manufactured home 

and must be installed in accordance with the 

manufacturer's instructions.

Cet appareil peut être installé cómme 

du matéri-el d'origine dans une maison 

préfabriquée  (É.U.  seulement)  ou  mobile 

et doit être installé selon les instructions 

du fabricant.

This appliance is only for use with the type of 

gas indicated on the rating plate. This appliance 

is not convertible for use with other gases.

Cet appareil doit être utilisé uniquement 

avec le type de gaz indiqué sur la plaque 

signalétique. Cet appareil ne peut être 

converti à d'autres gaz.

CAUTION: Ensure that the cross mem-
bers are not cut or weakened during 
installation. The structural integrity of 
the manufactured home floor, wall, and 
ceiling/roof must be maintained. 

CAUTION:  This appliance must be 
grounded to the chassis of the manu-
factured home in accordance with local 
codes or in the absence of local codes, 
with the National Electrical Code ANSI / 
NFPA 70 - latest edition.

LOCATION

In  selecting  the  location,  the  aesthetic  and 

functional use of the appliance are primary 

concerns.  However,  vent  system  routing  to 

the exterior and access to the fuel supply are 

also important. 

Due to high temperatures, the appliance 

should be located out of traffic and away from 

furniture and draperies (

Figure 2

). 

En raison des températures élevées, 

l’appareil devrait être installé dans un 

endroit où il y a peu de circulation et loin 

du mobilier et des tentures (

Figure 2

).

The location should also be free of electrical, 

plumbing or other heating/air conditioning 

ducting.

Recessed

Application

Cross Corner

Application

Flat

Application

Flat on W

all

Application

Room Divider

Application

Island

Application

Figure 2 - Typical Installation

Top of Fireplace 

Opening

Drywall

Noncombustible

horizontal

Termination

Fireplace

Be aware that this is a heat producing ap-

pliance. Objects placed above the unit are 

exposed to elevated temperatures.

Do not insulate the space between the appli-

ance and the area above it

The appliance must be mounted on a fully 

supported  base  extending  the  full  width  and 

depth of the unit. The appliance may be lo-

cated on or near conventional construction 

materials. However, if installed on combustible 

materials, such as carpeting, vinyl tile, or other 

combustible material other than wood flooring, 

the appliance shall be installed on a metal or 

wood panel extending the full width and depth 

of the appliance.

NOTE: When the unit is installed 

with one side flush with a wall, the 

wall on the other side of the unit 

must not extend beyond the front 

edge of the unit.

INNOVATIVE HEARTH PRODUCTS  •  POWER VENT DV GAS FIREPLACES  (DRT63__TYN / DRC63__TYN)  •  INSTALLATION INSTRUCTIONS

Содержание DRC6345TYNDRC6340TYN

Страница 1: ...E CHAUDE PEUT CAUSER DES BR LURES LAISSER REFROIDIR LA SURFACE VITR E AVANT D Y TOUCHER NE PERMETTEZ JAMAIS UN ENFANT DE TOUCHER LA SURFACE VITR E EL VIDRIO CALIENTE CAUSAR QUEMADURAS USTED DEBE NUNC...

Страница 2: ...peration Page 21 Step 9 Installing Logs Page 22 Step 10 Install Remove Glass Door Assembly Page 24 Step11 Burner Adjustments Page 24 Finishing Requirements Page 26 Step 12 Attaching Safety in Operatio...

Страница 3: ...WER VENT DV GAS FIREPLACES DRT63__TYN DRC63__TYN INSTALLATION INSTRUCTIONS WARNING Improper installation adjust ment alteration service or maintenance can cause injury or property damage Refer to this...

Страница 4: ...let and OUT for the manifold side see Figure 1 Orifice Sizes Sea Level To High Altitude These appliances are tested and approved for installation at elevations of 0 4500 ft 0 1370 m above sea level us...

Страница 5: ...actured home in accordance with local codes or in the absence of local codes with the National Electrical Code ANSI NFPA 70 latest edition LOCATION In selecting the location the aesthetic and function...

Страница 6: ...ead combustible projection of 2 1 2 64 mm or less see Figure 3 For projections exceeding 2 1 2 64 mm see Figure 3 For additional vent location restrictions refer to Figure 4 on Page 7 INNOVATIVE HEART...

Страница 7: ...s 10 000 BTU hr 3kW and 100 000 BTU hr 30kW 36 91 cm for appliances 100 000 BTU hr 30kW 6 15 2 cm for appliances 10 000 BTU hr 3kW 9 23 cm for appliances 10 000 BTU hr 3kW and 50 000 BTU hr 15kW 12 30...

Страница 8: ...rated 175 F or higher on the underside of the mantel MINIMUM CLEARANCES TO COMBUSTIBLES Appliance And Vent Clearances The appliance is approved with zero clearance to combustible materials on all sid...

Страница 9: ...low for a minimum clearance to combustible framing members as shown in Table 5 on Page 8 If the appliance is to be elevated above floor level a solid continuous platform must be constructed below the...

Страница 10: ...el No A B C D E F G H J 40 in in 50 5 8 37 1 4 42 7 8 25 5 16 34 37 5 8 33 3 32 29 9 32 34 3 4 mm 1286 946 1089 643 864 956 840 744 883 45 in in 56 11 16 42 1 4 47 7 8 28 3 8 40 1 8 43 5 8 38 3 32 34...

Страница 11: ...8 59 1 8 41 7 8 mm 1286 2124 1502 1064 45 in in 56 3 4 89 7 8 63 1 2 44 7 8 mm 1441 2283 1613 1140 C Back wall of chase enclosure including any finishing materials D A B Figure 9 Corner Framing with...

Страница 12: ...Fuel Gas Code ANSI Z223 1 NFPA 54 latest edition or Canada CAN CGA B149 1 latest edition These fireplaces are designed tested and listed for operation and installation only with Secure Vent SV4 5 and...

Страница 13: ...1 0 8 4 0 4 1 1 0 0 0 1 1 1 2 9 4 1 4 1 0 1 0 0 1 2 1 5 9 9 4 5 2 6 1 4 0 0 0 1 0 1 1 1 4 0 5 2 4 1 0 0 1 0 1 2 1 5 1 1 5 5 2 6 2 4 0 0 0 0 1 1 1 1 5 0 2 5 5 7 3 3 4 0 2 0 1 1 1 4 1 1 3 5 5 2 4 4 0 2...

Страница 14: ...x 1 2 screw may be used at the joint butitisnotrequiredasthepipewillsecurely lock when twisted C Attachventcomponentstoeachother Other vent sections may be added to the previously installedsectioninac...

Страница 15: ...Secure Vent firestop spacer must be used anytime vent pipe passes through a combustible wall Maintain the horizontal inclined run in a straight slightly elevated plane approximately 1 4 per foot 20 mm...

Страница 16: ...vent sections in horizontal inclined run as described in Step E Install support straps every three feet 1914 mm along horizontal inclined vent runs using conventional plumber s tape see Figure 16 on P...

Страница 17: ...TE Centerline of Vent Piping is NOT the Same as the Centerline of the Frame Opening 6 to 48 Vent Section Telescopic vent section Elbow or Appliance Collar Base of Appliance 3 76 mm 1 25 4 mm Adaptor S...

Страница 18: ...fireplace to the newly installed junction box near the termination Ensure the cable is safety plated to prevent damage from framing nails and finish drywall screws Route it into the lower control com...

Страница 19: ...n it to fit within the junction box cover WARNING Crimp connectors may be used on stranded cables such as SJOT cable only Solid wire Romex must be connected per the National Electric Code NEC 70 lates...

Страница 20: ...t only be replaced as a complete unit as provided by the manufacturer Do not attempt to replace broken cracked or chipped glass separately INNOVATIVE HEARTH PRODUCTS POWER VENT DV GAS FIREPLACES DRT63...

Страница 21: ...ed above C When the gas lines are tested and leak free be sure to rinse off the leak testing solution D Re install the access plate making certain the gasket has not been damaged Figure 29 Fireplace R...

Страница 22: ...able and attractive flame pattern Any attempt to use a different log set in the fireplace will void the warranty and will result in incomplete combustion sooting and poor flame quality Logs get very h...

Страница 23: ...e And Push It Towards The Rear 3 2 4 1 6 5 7 Log Number Description 1 Log Center 2 Log Rear 3 Log Center Left 4 Log Center Right 5 Log Rear Top 6 Log Front Left 7 Log Front Center Table 6 Log Set Alig...

Страница 24: ...st be replaced prior to operating the appliance AVERTISSEMENT Tout cran ou pro tecteurretir pourpermettrel entretiende l appareil doit tre remis en place avant de mettre l appareil en marche Installin...

Страница 25: ...nstallation Leave the ON REMOTE OFF wall switch in the REMOTE position and turn the remote switch OFF Use the remote to adjust the flame height as desired CAUTION Soot will be produced if the air shut...

Страница 26: ...ed there are two methods of installation Combustible or noncombustible finish material may abut the front face of the fireplace and the floor panel see Figure 45 Combustible or noncombustible finish m...

Страница 27: ...ipalement parl e dans la r sidence du propri taire En cas de doute collez l tiquette en anglais 2 Rep rezlat l commandeetnettoyez lasoigneuse ment pour liminer la poussi re et les traces degraisseoud...

Страница 28: ...Section 77L72 SV4 5L24 24 610mm Vent Section 77L73 SV4 5L36 36 914mm Vent Section 77L74 SV4 5L48 48 1219mm Vent Section 77L75 SV4 5LA Telescopic Section 77L76 SV4 5E45 45 Degree Elbow 77L77 SV4 5E90 9...

Отзывы: