background image

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

21

Figure 31 - Electronic Pilot 

Assembly - Proper Pilot 

Flame Appearance

Pilot

Nozzels

Flame

Sensor

Pilot hood

Igniter

Rod

     

WARNING

Never use an open flame to 

check for leaks.

Turn on gas supply and test for gas leaks using 

a  gas  leak  test  solution  (also  referred  to  as 

bubble leak solution).

Step 6. CONNECTING GAS LINE 

 

All codes require a shut-off valve mounted in 

the supply line. The orientation of the shut-off 

valve should face the front. Figure 30  illustrates 

two methods for connecting the gas supply. 

A Sediment Trap is recommended to prevent 

moisture and debris in gas line from damaging 

the valve.

The flex-line method is acceptable in the USA 

where local codes permit. Installation must be in 

compliance with local codes. These appliances 

are  equipped  with  a  gas  flex-line  for  use  in 

connecting the unit to the gas line.See Figure 

30

 for flex-line description. 

A manual shutoff valve is also provided with 

the flex-line. The gas control valve is located 

on the right side of the unit.

When using solid gas line connector, access 

the valve by removing the front door assembly 

on the valve access side and the access plate 

(see

 Figure 29).

The electronic control valve has a 3/8" (10 mm) 

NPT thread gas supply inlet. 

Secure all joints tightly using appropriate 

tools and sealing compounds. 

Bring the shutoff valve on the end of the flex-line 

over to the hard pipe and tighten with wrenches 

from above through the firebox opening.

  NOTE: Using a soapy water solution is 

an effective leak test solution but it is not 

recommended, because the soap residue 

that is left on the pipes/fittings can result in 

corrosion over time. 

A. Light  the  appliance  (refer  to  the  lighting 

instructions label in control compartment 

or in the Care and Operation instructions 

manual).

B.

 Brush all joints and connections with the 

gas leak test solution to check for leaks. 

TEST ALL CONNECTIONS FOR GAS LEAKS 

(FACTORY AND FIELD)

  If bubbles are formed, or gas odor is detected, 

turn the unit off. Either tighten or refasten the 

leaking connection, then retest as described 

above.

C. When the gas lines are tested and leak free 

be sure to rinse off the leak testing solution. 

D. Re-install the access plate, making certain 

the gasket has not been damaged. 

Figure 29 - Fireplace Right Side

Right Side

Modesty Panel

Access Plate

Gas Valve

NOTE: The gas supply line 

must be installed in accor-

dance with building codes 

by a qualified installer ap-

proved  and/or  licensed  as 

required by the locality. In 

the Commonwealth of Mas-

sachusetts, installation must 

be performed by a licensed 

plumber or gas fitter.

Figure 30 - Gas Connection

Gas

Valve

3/8” NPT  x

Flare Fitting 

3/8” Flex Tubing

3/8” Nipple

3/8” Union

3/8” Close 

Nipple

3/8” Shut-off Valve

1/2” x 3/8”

Reducer

Gas 

Stub 

1/2 x 3/8” Flare

Shut-off Valve

Gas Solid Line Connector

Gas Flex Line Connector

*Sediment

   Trap

3 in.

Min

Gas Shutoff 

Valve

INNOVATIVE HEARTH PRODUCTS  •  POWER VENT DV GAS FIREPLACES  (DRT63__TYN / DRC63__TYN)  •  INSTALLATION INSTRUCTIONS

Step 7. INSTALL FIREBOX LINER KIT

Install  the  firebox  liner  kit  per  the  included 

instructions.

Step 8. VERIFYING APPLIANCE 
OPERATION

Turn on burner then observe the individual 

tongues of flame on the burner. Make sure all 

ports are open and producing flame evenly 

across the burner. If any ports are blocked, or 

partially blocked, clean out the ports.

With  gas  line  installed  run  initial  system 

checkout before closing up the front of the unit. 

Follow the pilot lighting instructions provided.

NOTE: Lighting Instructions are also found on 

the literature tag tied to the bracket above the 

gas valve. To access the tag, reach into the 

right side opening.

When first lighting the appliance, it will take a few 

minutes for the line to purge itself of air. Once 

purging is complete, the pilot and burner will 

light and operate as indicated in the instruction 

manual. Subsequent lighting of the appliance 

will not require such purging. Inspect the pilot 

flame  (remove  logs,  if  necessary,  handling 

carefully).

Electronic Appliance Checkout

To light the burner, turn the ON/REMOTE/OFF 

wall switch or remote control to the ON posi-

tion. Ensure the igniter lights the pilot. The pilot 

flame should engulf the flame sensor as shown 

in Figure 31.

NOTE: The control must detect the pressure 

switch in the open state, at startup, and then 

close after the blower starts.

Содержание DRC6345TYNDRC6340TYN

Страница 1: ...E CHAUDE PEUT CAUSER DES BR LURES LAISSER REFROIDIR LA SURFACE VITR E AVANT D Y TOUCHER NE PERMETTEZ JAMAIS UN ENFANT DE TOUCHER LA SURFACE VITR E EL VIDRIO CALIENTE CAUSAR QUEMADURAS USTED DEBE NUNC...

Страница 2: ...peration Page 21 Step 9 Installing Logs Page 22 Step 10 Install Remove Glass Door Assembly Page 24 Step11 Burner Adjustments Page 24 Finishing Requirements Page 26 Step 12 Attaching Safety in Operatio...

Страница 3: ...WER VENT DV GAS FIREPLACES DRT63__TYN DRC63__TYN INSTALLATION INSTRUCTIONS WARNING Improper installation adjust ment alteration service or maintenance can cause injury or property damage Refer to this...

Страница 4: ...let and OUT for the manifold side see Figure 1 Orifice Sizes Sea Level To High Altitude These appliances are tested and approved for installation at elevations of 0 4500 ft 0 1370 m above sea level us...

Страница 5: ...actured home in accordance with local codes or in the absence of local codes with the National Electrical Code ANSI NFPA 70 latest edition LOCATION In selecting the location the aesthetic and function...

Страница 6: ...ead combustible projection of 2 1 2 64 mm or less see Figure 3 For projections exceeding 2 1 2 64 mm see Figure 3 For additional vent location restrictions refer to Figure 4 on Page 7 INNOVATIVE HEART...

Страница 7: ...s 10 000 BTU hr 3kW and 100 000 BTU hr 30kW 36 91 cm for appliances 100 000 BTU hr 30kW 6 15 2 cm for appliances 10 000 BTU hr 3kW 9 23 cm for appliances 10 000 BTU hr 3kW and 50 000 BTU hr 15kW 12 30...

Страница 8: ...rated 175 F or higher on the underside of the mantel MINIMUM CLEARANCES TO COMBUSTIBLES Appliance And Vent Clearances The appliance is approved with zero clearance to combustible materials on all sid...

Страница 9: ...low for a minimum clearance to combustible framing members as shown in Table 5 on Page 8 If the appliance is to be elevated above floor level a solid continuous platform must be constructed below the...

Страница 10: ...el No A B C D E F G H J 40 in in 50 5 8 37 1 4 42 7 8 25 5 16 34 37 5 8 33 3 32 29 9 32 34 3 4 mm 1286 946 1089 643 864 956 840 744 883 45 in in 56 11 16 42 1 4 47 7 8 28 3 8 40 1 8 43 5 8 38 3 32 34...

Страница 11: ...8 59 1 8 41 7 8 mm 1286 2124 1502 1064 45 in in 56 3 4 89 7 8 63 1 2 44 7 8 mm 1441 2283 1613 1140 C Back wall of chase enclosure including any finishing materials D A B Figure 9 Corner Framing with...

Страница 12: ...Fuel Gas Code ANSI Z223 1 NFPA 54 latest edition or Canada CAN CGA B149 1 latest edition These fireplaces are designed tested and listed for operation and installation only with Secure Vent SV4 5 and...

Страница 13: ...1 0 8 4 0 4 1 1 0 0 0 1 1 1 2 9 4 1 4 1 0 1 0 0 1 2 1 5 9 9 4 5 2 6 1 4 0 0 0 1 0 1 1 1 4 0 5 2 4 1 0 0 1 0 1 2 1 5 1 1 5 5 2 6 2 4 0 0 0 0 1 1 1 1 5 0 2 5 5 7 3 3 4 0 2 0 1 1 1 4 1 1 3 5 5 2 4 4 0 2...

Страница 14: ...x 1 2 screw may be used at the joint butitisnotrequiredasthepipewillsecurely lock when twisted C Attachventcomponentstoeachother Other vent sections may be added to the previously installedsectioninac...

Страница 15: ...Secure Vent firestop spacer must be used anytime vent pipe passes through a combustible wall Maintain the horizontal inclined run in a straight slightly elevated plane approximately 1 4 per foot 20 mm...

Страница 16: ...vent sections in horizontal inclined run as described in Step E Install support straps every three feet 1914 mm along horizontal inclined vent runs using conventional plumber s tape see Figure 16 on P...

Страница 17: ...TE Centerline of Vent Piping is NOT the Same as the Centerline of the Frame Opening 6 to 48 Vent Section Telescopic vent section Elbow or Appliance Collar Base of Appliance 3 76 mm 1 25 4 mm Adaptor S...

Страница 18: ...fireplace to the newly installed junction box near the termination Ensure the cable is safety plated to prevent damage from framing nails and finish drywall screws Route it into the lower control com...

Страница 19: ...n it to fit within the junction box cover WARNING Crimp connectors may be used on stranded cables such as SJOT cable only Solid wire Romex must be connected per the National Electric Code NEC 70 lates...

Страница 20: ...t only be replaced as a complete unit as provided by the manufacturer Do not attempt to replace broken cracked or chipped glass separately INNOVATIVE HEARTH PRODUCTS POWER VENT DV GAS FIREPLACES DRT63...

Страница 21: ...ed above C When the gas lines are tested and leak free be sure to rinse off the leak testing solution D Re install the access plate making certain the gasket has not been damaged Figure 29 Fireplace R...

Страница 22: ...able and attractive flame pattern Any attempt to use a different log set in the fireplace will void the warranty and will result in incomplete combustion sooting and poor flame quality Logs get very h...

Страница 23: ...e And Push It Towards The Rear 3 2 4 1 6 5 7 Log Number Description 1 Log Center 2 Log Rear 3 Log Center Left 4 Log Center Right 5 Log Rear Top 6 Log Front Left 7 Log Front Center Table 6 Log Set Alig...

Страница 24: ...st be replaced prior to operating the appliance AVERTISSEMENT Tout cran ou pro tecteurretir pourpermettrel entretiende l appareil doit tre remis en place avant de mettre l appareil en marche Installin...

Страница 25: ...nstallation Leave the ON REMOTE OFF wall switch in the REMOTE position and turn the remote switch OFF Use the remote to adjust the flame height as desired CAUTION Soot will be produced if the air shut...

Страница 26: ...ed there are two methods of installation Combustible or noncombustible finish material may abut the front face of the fireplace and the floor panel see Figure 45 Combustible or noncombustible finish m...

Страница 27: ...ipalement parl e dans la r sidence du propri taire En cas de doute collez l tiquette en anglais 2 Rep rezlat l commandeetnettoyez lasoigneuse ment pour liminer la poussi re et les traces degraisseoud...

Страница 28: ...Section 77L72 SV4 5L24 24 610mm Vent Section 77L73 SV4 5L36 36 914mm Vent Section 77L74 SV4 5L48 48 1219mm Vent Section 77L75 SV4 5LA Telescopic Section 77L76 SV4 5E45 45 Degree Elbow 77L77 SV4 5E90 9...

Отзывы: