14

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

Figure 12 - Framing Ceiling Opening

A.

 

Frame ceiling opening - 

Use a plumb line 

from the ceiling above the appliance to locate 

center of the vertical run. Cut and/or frame 

an opening, 10-1/2" x 10-1/2" (267 mm x 267 

mm) inside dimensions, about this center mark 

(Figure 12).

Figure 13 - Attaching the Vent Adaptor

Align the dimple (four places) of the 

upper vent section with the opening 

of the locking incline channel on 

the lower vent section or appliance 

collar. Twist vent component 

clockwise to engage and seal until 

arrow and dimple align.

Dimple

Locking Incline 

Channel

Connected Vent 

Sections

Arrow

Arrow

Adaptor on Appliance Collar 

or Vent Section

B.

 

Attach adaptor (with probe) to appliance 

collar - 

Secure Vent

®

 SV4.5 direct-vent sys-

tem components are unitized concentric pipe 

components featuring positive twist lock con-

nections (see

 Figure 13).

All of the appliances covered in this document 

are fitted with collars having locking inclined 

channels. The dimpled end of the adaptor fits 

over the appliance collar to create the positive 

twist lock connection.

10-1/2" min. 

(267 mm)

Ceiling Framing

Plumb Bob

10-1/2" min. 

(267 mm)

To attach a vent component to the adaptor on 

appliance collar, align the dimpled end over the 

adaptor collar, adjusting the radial alignment 

until the four locking dimples are aligned with the 

inlet of the four inclined channels on the collar 

(refer to 

Figure 13

). Push the vent component 

against the collar until it fully engages, then twist 

the component clockwise, running the dimples 

down and along the incline channels until they 

seat at the end of the channels. 

Support the vertical portion of the venting 

system every eight feet (2.4 m) above the 

fireplace vent outlet.

 One method of support 

is  by  utilizing  field  provided  support  straps 

(conventional  plumber's  tape).  Secure  the 

plumber's tape to the framing members with 

nails or screws. 

Strap the tape around the vent, 

securing the ends of the tape to the framing. 

If desired, sheet metal screws #6 x 1/2" length 

may be used to secure the support straps to 

the vent pipe. 

F. Change vent direction to horizontal/inclined 

run - 

At transition from or to a horizontal/in-

clined run, install the SV4.5E45 and SV4.5E90 

elbows in the same manner as the straight vent 

sections. The elbows feature a twist section to 

allow them to be routed about the center axis 

of their initial collar section to align with the 

required direction of the next vent run element. 

Twist elbow sections in a clockwise direction 

only so as to avoid the possibility of unlocking 

any of the previously connected vent sections 

(see

 Figures 13 and 15).

The unitized design of the Secure Vent

®

 com-

ponents will engage and seal both the inner and 

outer pipe without the need for sealant or screws. 

If desired a #6 x 1/2" screw may be used at the 

joint, but it is not required as the pipe will securely 

lock when twisted.

C. Attach vent components to each other - 

Other 

vent sections may be added to the previously 

installed section in accordance with the require-

ments shown in Figures 16 and 17 on Page 15.
To add another vent component to a length of 

vent run, align the dimpled end over the inclined 

channel end of the previously installed section, 

adjusting the radial alignment until the four 

locking dimples are aligned with the inlets of 

the four incline channels of the previous section. 
Push the vent component against the previ-

ous  section  until  it  fully  engages,  then  twist 

the component clockwise running the dimples 

down and along the incline channels until they 

seat at the end of the channels. 

This seating 

position is indicated by the alignment of the 

arrow and dimple as shown in

 Figure 13.

D.

 

Install firestop/spacer at ceiling - When 

using Secure Vent, use SV4.5VF firestop/spacer 

at ceiling joists. If there is living space above 

the ceiling level, the firestop/spacer must be 

installed on the bottom side of the ceiling. If 

attic space is above the ceiling, the firestop/

spacer must be installed on the top side of 

the joist. Route the vent sections through the 

framed opening and secure the firestop/spacer 

with 8d nails or other appropriate fasteners at 

each corner.

Maintain 1" (25 mm) clearance to combus-

tibles, framing members, and attic or ceiling 

insulation when running vertical chimney 

sections. Attic insulation shield (h3907) may 

be used to obtain the required clearances 

indicated here. See installation accessories 

on 

Page 28

. The gap between the vent pipe 

and a vertical firestop may be sealed with 

noncombustible caulking.
E.

 

Support the vertical vent run sections -

8-1/8”

(206 mm)

4-13/16”

(122 mm)

Swivel Joint

(360° swivel)

SV4.5E45

45° Elbow)

Swivel Joint

(360° swivel)

SV4.5E90

90° Elbow)

G.

 

Continue installation of horizontal/inclined 

sections - 

Continue with the installation of the 

straight vent sections in horizontal/inclined run 

as described in 

Step C.

 Install support straps 

every  three  feet  (914  mm)  along  horizontal/

inclined vent runs using conventional plumber’s 

tape 

(

Figure 16 on Page 15

)

NOTE: Maintain the horizontal/inclined run in 

a straight, slightly elevated plane - approxi-

mately 1/4" per foot (20 mm per meter) - in 

a direction away from the fireplace. Smaller 

rise per foot run ratios are acceptable, down 

to at or near level. Use a carpenter’s level to 

measure from a constant surface and adjust 

the support straps as necessary.

NOTE: Maintain the required clearances to 

combustibles: 1" (25 mm) at all sides for all 

vertical runs; and 3" (76 mm) at the top, 1" (25 

mm) at sides, and 1" (25 mm) at the bottom 

for all horizontal/inclined runs.

Blocking

Support Straps

(Plumber's 

tape)

8' (2.4 m)

Maximum

1/2" (13 mm) 

minimum 

clearance to 

combustibles

Figure 14 - Supporting Vertical Vents

Figure 15 - Vent Elbow Sections

INNOVATIVE HEARTH PRODUCTS  •  POWER VENT DV GAS FIREPLACES  (DRT63__TYN / DRC63__TYN)  •  INSTALLATION INSTRUCTIONS

Содержание DRC6345TYNDRC6340TYN

Страница 1: ...E CHAUDE PEUT CAUSER DES BR LURES LAISSER REFROIDIR LA SURFACE VITR E AVANT D Y TOUCHER NE PERMETTEZ JAMAIS UN ENFANT DE TOUCHER LA SURFACE VITR E EL VIDRIO CALIENTE CAUSAR QUEMADURAS USTED DEBE NUNC...

Страница 2: ...peration Page 21 Step 9 Installing Logs Page 22 Step 10 Install Remove Glass Door Assembly Page 24 Step11 Burner Adjustments Page 24 Finishing Requirements Page 26 Step 12 Attaching Safety in Operatio...

Страница 3: ...WER VENT DV GAS FIREPLACES DRT63__TYN DRC63__TYN INSTALLATION INSTRUCTIONS WARNING Improper installation adjust ment alteration service or maintenance can cause injury or property damage Refer to this...

Страница 4: ...let and OUT for the manifold side see Figure 1 Orifice Sizes Sea Level To High Altitude These appliances are tested and approved for installation at elevations of 0 4500 ft 0 1370 m above sea level us...

Страница 5: ...actured home in accordance with local codes or in the absence of local codes with the National Electrical Code ANSI NFPA 70 latest edition LOCATION In selecting the location the aesthetic and function...

Страница 6: ...ead combustible projection of 2 1 2 64 mm or less see Figure 3 For projections exceeding 2 1 2 64 mm see Figure 3 For additional vent location restrictions refer to Figure 4 on Page 7 INNOVATIVE HEART...

Страница 7: ...s 10 000 BTU hr 3kW and 100 000 BTU hr 30kW 36 91 cm for appliances 100 000 BTU hr 30kW 6 15 2 cm for appliances 10 000 BTU hr 3kW 9 23 cm for appliances 10 000 BTU hr 3kW and 50 000 BTU hr 15kW 12 30...

Страница 8: ...rated 175 F or higher on the underside of the mantel MINIMUM CLEARANCES TO COMBUSTIBLES Appliance And Vent Clearances The appliance is approved with zero clearance to combustible materials on all sid...

Страница 9: ...low for a minimum clearance to combustible framing members as shown in Table 5 on Page 8 If the appliance is to be elevated above floor level a solid continuous platform must be constructed below the...

Страница 10: ...el No A B C D E F G H J 40 in in 50 5 8 37 1 4 42 7 8 25 5 16 34 37 5 8 33 3 32 29 9 32 34 3 4 mm 1286 946 1089 643 864 956 840 744 883 45 in in 56 11 16 42 1 4 47 7 8 28 3 8 40 1 8 43 5 8 38 3 32 34...

Страница 11: ...8 59 1 8 41 7 8 mm 1286 2124 1502 1064 45 in in 56 3 4 89 7 8 63 1 2 44 7 8 mm 1441 2283 1613 1140 C Back wall of chase enclosure including any finishing materials D A B Figure 9 Corner Framing with...

Страница 12: ...Fuel Gas Code ANSI Z223 1 NFPA 54 latest edition or Canada CAN CGA B149 1 latest edition These fireplaces are designed tested and listed for operation and installation only with Secure Vent SV4 5 and...

Страница 13: ...1 0 8 4 0 4 1 1 0 0 0 1 1 1 2 9 4 1 4 1 0 1 0 0 1 2 1 5 9 9 4 5 2 6 1 4 0 0 0 1 0 1 1 1 4 0 5 2 4 1 0 0 1 0 1 2 1 5 1 1 5 5 2 6 2 4 0 0 0 0 1 1 1 1 5 0 2 5 5 7 3 3 4 0 2 0 1 1 1 4 1 1 3 5 5 2 4 4 0 2...

Страница 14: ...x 1 2 screw may be used at the joint butitisnotrequiredasthepipewillsecurely lock when twisted C Attachventcomponentstoeachother Other vent sections may be added to the previously installedsectioninac...

Страница 15: ...Secure Vent firestop spacer must be used anytime vent pipe passes through a combustible wall Maintain the horizontal inclined run in a straight slightly elevated plane approximately 1 4 per foot 20 mm...

Страница 16: ...vent sections in horizontal inclined run as described in Step E Install support straps every three feet 1914 mm along horizontal inclined vent runs using conventional plumber s tape see Figure 16 on P...

Страница 17: ...TE Centerline of Vent Piping is NOT the Same as the Centerline of the Frame Opening 6 to 48 Vent Section Telescopic vent section Elbow or Appliance Collar Base of Appliance 3 76 mm 1 25 4 mm Adaptor S...

Страница 18: ...fireplace to the newly installed junction box near the termination Ensure the cable is safety plated to prevent damage from framing nails and finish drywall screws Route it into the lower control com...

Страница 19: ...n it to fit within the junction box cover WARNING Crimp connectors may be used on stranded cables such as SJOT cable only Solid wire Romex must be connected per the National Electric Code NEC 70 lates...

Страница 20: ...t only be replaced as a complete unit as provided by the manufacturer Do not attempt to replace broken cracked or chipped glass separately INNOVATIVE HEARTH PRODUCTS POWER VENT DV GAS FIREPLACES DRT63...

Страница 21: ...ed above C When the gas lines are tested and leak free be sure to rinse off the leak testing solution D Re install the access plate making certain the gasket has not been damaged Figure 29 Fireplace R...

Страница 22: ...able and attractive flame pattern Any attempt to use a different log set in the fireplace will void the warranty and will result in incomplete combustion sooting and poor flame quality Logs get very h...

Страница 23: ...e And Push It Towards The Rear 3 2 4 1 6 5 7 Log Number Description 1 Log Center 2 Log Rear 3 Log Center Left 4 Log Center Right 5 Log Rear Top 6 Log Front Left 7 Log Front Center Table 6 Log Set Alig...

Страница 24: ...st be replaced prior to operating the appliance AVERTISSEMENT Tout cran ou pro tecteurretir pourpermettrel entretiende l appareil doit tre remis en place avant de mettre l appareil en marche Installin...

Страница 25: ...nstallation Leave the ON REMOTE OFF wall switch in the REMOTE position and turn the remote switch OFF Use the remote to adjust the flame height as desired CAUTION Soot will be produced if the air shut...

Страница 26: ...ed there are two methods of installation Combustible or noncombustible finish material may abut the front face of the fireplace and the floor panel see Figure 45 Combustible or noncombustible finish m...

Страница 27: ...ipalement parl e dans la r sidence du propri taire En cas de doute collez l tiquette en anglais 2 Rep rezlat l commandeetnettoyez lasoigneuse ment pour liminer la poussi re et les traces degraisseoud...

Страница 28: ...Section 77L72 SV4 5L24 24 610mm Vent Section 77L73 SV4 5L36 36 914mm Vent Section 77L74 SV4 5L48 48 1219mm Vent Section 77L75 SV4 5LA Telescopic Section 77L76 SV4 5E45 45 Degree Elbow 77L77 SV4 5E90 9...

Отзывы: