9 Reactive Power Regulation
table 8-7
Description of reactive power regulation
P
Pa
arra
am
me
ette
err
D
De
essc
crriip
pttiio
on
n
D
De
effa
au
ulltt
R
Ra
an
ng
ge
e
R
Re
ea
ac
cttiivve
e P
Po
ow
we
err
S
Se
ettttiin
ng
g
P
Pe
errssiisstte
en
nc
ce
e
Switch for activating/deactivating the
function of reactive power setting
persistence
On
On / Off
R
Re
ea
ac
cttiivve
e P
Po
ow
we
err
R
Re
eg
gu
ulla
attiio
on
n M
Mo
od
de
e
-
Off
Off / PF /
Qt / Q(P) /
Q(U)
table 8-8
Descriptions of reactive power regulation mode:
M
Mo
od
de
e
D
De
essc
crriip
pttiio
on
nss
Off
The PF is fixed at +1.000.
PF
The reactive power can be regulated by the parameter PF (Power
Factor).
Qt
The reactive power can be regulated by the parameter Q-Var limits (in
%).
Q(P)
The PF changes with the output power of the inverter.
Q(U)
The reactive power changes with the grid voltage.
“
“O
Offff”
” M
Mo
od
de
e
The reactive power regulation function is disabled. The PF is limited to +1.000.
“
“P
PF
F”
” M
Mo
od
de
e
The power factor is fixed and reactive power setpoint is calculated according to the cur-
rent power. The PF ranges from 0.8 leading to 0.8 lagging.
Leading: the inverter is sourcing reactive power to the grid.
Lagging: the inverter is injecting reactive power into the grid.
“
“Q
Qtt”
” M
Mo
od
de
e
In the Qt mode, system rated reactive power is fixed, and the system injects reactive
power according to the delivered reactive power ratio. The R
Re
ea
ac
cttiivve
e P
Po
ow
we
err R
Ra
attiio
o is set
through the App.
The setting range of the reactive power ratio is 0~100% or 0~-100%, corresponding to
the ranges of inductive and capacitive reactive power regulation respectively.
“
“Q
Q((P
P))”
” M
Mo
od
de
e
The PF of the inverter output varies in response to the output power of the inverter.