47
A two-pole DC circuit breaker with overcurrent protection (voltage rating not
less than 100 V and current rating not less than 100 A) should be installed be-
tween the inverter and the battery.
If the battery is integrated with a readily accessible internal DC breaker, no addi-
tional DC breaker is required.
All power cables are equipped with water-proof direct plug-in connectors, which match
the battery terminals at the bottom of the inverter.
6.9.1.1 Assembling the SUNCLIX Connector
During assembly, be careful not to contaminate, pull out, or shift, the seal in the
cable gland. A contaminated or shifted seal impairs strain relief and leak
tightness.
ffiig
gu
urre
e 6
6--4
4 SUNCLIX Connector Components
1:Spring
2: Sleeve
3: Insert
4: Cable gland
step 1
Strip the insulation from the cable by 15 mm.
step 2
Pry the connection open and pull the sleeve and the insert apart.
User Manual