70
Outer Diameter D(mm)
Sealing Rings
4.5 ~ 6
c
6 ~ 12
a + b
12 ~ 18
b
step 3 Strip the insulation layer of the Ethernet cable with a wire stripper, and insert the signal wires
to the RJ45 connector. Crimp the RJ45 connector with a crimping tool.
Pin
Assignment for inverters capable of both charging and
discharging
1
DRM 1/5
2
DRM 2/6
3
DRM 3/7
4
DRM 4/8
5
RefGen
6
Com/DRM0
7
V+
8
V-
step 4 Insert the RJ45 connector to the RJ45 jack.
step 5 Install the communication junction box, referring to
Install the Communication Junction
step 6 Pull slightly the cable backward and screw the swivel nut clockwise.