![Sungrow SG110CX-P2 Скачать руководство пользователя страница 103](http://html.mh-extra.com/html/sungrow/sg110cx-p2/sg110cx-p2_user-manual_1396675103.webp)
93
Parameter
Explanation
Range
QU_Q3
Value of Q/Sn at P3 on the Q(U) mode
curve
-60% ~ 60%
QU_V4
Grid voltage limit at P4 on the Q(U) mode
curve
100% ~ 120%
QU_Q4
Value of Q/Sn at P4 on the Q(U) mode
curve
0 ~ 60%
QU_EnterPower
Active power for Q(U) function activation
20% ~ 100%
QU_ExitPower
Active power for Q(U) function deactivation
1% ~ 20%
QU_EnableMode
Unconditional activation/deactivation of Q
(U) function
Yes / No / Yes,
Limited by PF
QU_Limited PF
Value
PF value for Q(U) function activation
0~0.95
* Curve C is reserved and consistent with Curve A currently.
figure 7-20
Q(U) Curve
7.8.4 Communication Parameters
Serial Port Parameters
Tap
Settings→Communication Parameters→Serial Port Parameters
to enter the corre-
sponding screen, as shown in the following figure. The device address ranges from 1 to 246.
figure 7-21
Serial Port Parameters
7.8.5 Firmware Update
To avoid download failure due to poor on-site network signal, it is recommended to download
the firmware package to the mobile device in advance.
Perform firmware update only during high irradiance conditions in order to prevent equip-
ment failure.
step 1 Enable the "Mobile data" of the mobile device.
User Manual