90
figure 7-18
Reactive Power Regulation
table 7-8 Reactive Power Regulation
Parameter
Definition/Setting
Description
Range
Reactive power gener-
ation at night
Switch for enabling/disabling
Q at night function.
Enable/Disable
Reactive power ratio
at night
Reactive power ratio set for
the Q at night function.
-100%~0%/
0%~100%
Reactive power setting
persistence
Switch for enabling/disabling
the power-off function during
reactive power
Enable/Disable
Closed-loop control
reactive power
regulation
Switch for closed-loop control
during reactive power
Enable/Disable
Reactive power regu-
lation mode
Reactive power regulation
mode selection
Off/PF/Qt/Q(P)/Q(U)
The inverter provides the reactive power regulation function. Enable this function under
Re-
active Power Regulation Mode
and select the appropriate mode.
table 7-9 Descriptions of reactive power regulation mode:
Mode
Descriptions
Off
The PF is fixed at +1.000.
PF
The reactive power can be regulated by the parameter PF (Power Factor).
User Manual