10
Symbol
Explanation
Danger to life due to high voltages!
Do not touch live parts for 5 minutes after disconnection from
the power sources.
Only qualified personnel can open and maintain the inverter.
Additional grounding point.
Read the user manual before maintenance!
* The table shown here is for reference only. The actual product received may differ.
2.4
LED Indicator
The LED indicator on the front of the inverter indicates the working state of the inverter.
table 2-1 State description of the LED indicator
LED color
State
Definition
Blue
On
The device is connected to the grid and operating
normally.
Fast blink
(Period: 0.2s)
The Bluetooth communication is connected and there
is data communication.
No system fault occurs.
Slow blink
(Period: 2s)
The device is in standby or startup state (not feeding
power into the grid).
Slow blink
once, fast
blink three
times
The inverter is performing PID recovery.
Red
On
A fault occurs and the device cannot connect to the
grid.
Twinkling
The Bluetooth connection is established, data commu-
nication in process, and a system fault occurs.
Gray
OFF
Both the AC and DC sides are powered down.
User Manual