67
AC-Side Requirements
DC-Side Requirements
Max. voltage: 230 Vac
Max. current: 3 A
Max. voltage: 24 Vdc
Max. current: 3 A
DI terminal (emergency stop dry contact)
The dry contact can be configured to be an emergency stop contact.
When the DI contact and PGND contact are shorted by external controlled switch (The ex-
ternal switch can be configured as normally open contact or normally closed contact), the in-
verter will immediately shutdown.
NS Protection
NS Protection is used for German market currently. For a plant with an installed power over
30kW, an external NS Protection Relay is connected to inverters that are connected to each
other with NS Protection terminals. When the grid runs abnormally, the status of the relay's
dry contact changes, and the inverters are emergently shut down.
NS Protection (including Passive Valid) can be set. When NS Protection is enabled on the
iSolarCloud, the inverters will operate normally when DI contact and PGND contact are
shorted by external controlled switch, and the inverters will emergently stop when DI contact
and PGND contact are disconnected.
The dry contacts only support passive switch signal input.
The following figure shows the typical application of local stop dry contact.